2022-07-05 10:39:55 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. REVISION: 22041143 |
| W. P. B. PERMIT: 21051228 |
| ADD: 424 PRK PLACE |
| CONT: HEDRICK BROTHERS |
| TEL: 561-578-1602 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| PERMIT: 21051228 SHEET G0.04 CODE DATA: |
| AREA LIMITATIONS: A-2 OCCUPANCY, TYPE VB CONSTRUCTION, |
| FIRE SPRINKLERED |
| BUILDING OCCUPANCIES: A-2 RESTAURANT, M MERCANTILE, B |
| BUSINESS & S-2 BACK OF HOUSE STORAGE |
| |
| 3RD REVIEW REVISION: 22041143 TENANT BUILDOUT |
| DATE: TUES. JULY 05TH/ 2022 |
| ACTION: DENIED |
| |
| |
| |
| 1) SHEET G1-01 LIFE SAFETY PLAN: |
| 1A) 3RD ROUND OF COMMENTS!!!!! TENANT SPACE # 6 SHOWS |
| ALL OF THE TENANTS EXITING OUT OF THIS SPACE INTO |
| CORRIDOR # 17. THE OCCUPANT LOAD FOR THIS MERCANTILE |
| OCCUPANCY IS 98 OCCUPANTS, PLUS ? (57) OCCUPANTS OF THE |
| OCCUPANT LOAD FROM TENANT SPACE 5 IS ALSO EXITING |
| THROUGH TENANT SPACE 6 THE WAY THE EXIT DIRECTIONAL |
| LIGHTSARE POSITONED AND DOOR SWING. 2010 FBC-B SECTION |
| 1006.2.1 & TABLE 1006.2.1. WHEN A OCCUPANT LOAD OF MORE |
| THAN 49 IS REACHED 2 MEANS OF EGRESS ARE REQUIRED, YOU |
| CAN NOT USE THE ONE CORRIDOR FOR ALL OF THE OCCUPANTS. |
| PLEASE NOTE IN THE ORIGINAL BUILDING SHELL DESIGN NONE |
| OF THE TENANTS ON THE LEFT SIDE OF THE BUILDING HAD A |
| OCCUPANT LOAD GREATER THAN 49. |
| |
| 1B) 3RD REQUEST. THE LIFE SAFETY SHEET DOES NOT PROVIDE |
| DIMENSIONS FOR EITHER PORTION OF CORRIDOR # 17. SHEET |
| A1-01 DIMENSIONS FROM THE EXTERIOR WALL TO THE INSIDE |
| (TENANT SIDE) OF THE CORRIDOR WALL TO DETERMINE CODE |
| COMPLIANCE FOR SIZING MEANS OF EGRESS. 2010 |
| FBC-BUILDING SECTIONS 1005.3.1 & 1005.3.2. WE ARE |
| LOOKING WORST CASE SCENARIO AN A2 ASSEMBLY OCCUPANCY |
| FOR TENANT SPACES 4, 5AND 6.. * TENANT SPACE MAY CHANGE |
| PER FUTURE TENANT BUILDOUT OF SPACE. |
| |
| 1C) 3RD REQUEST. THE CORRIDOR # 17 SERVES AS THE MEANS |
| OF EGRESS AS SHOWN FOR TENANT 4 (1/2 OF OCC. LOAD), |
| TENANT 5 (1/2 OF OCCUPANT LOAD) ALL OF TENANT 6 NEEDS |
| TO CHANGE AND ALL OF TENANT 7, PROVIDE THE TOTAL |
| OCCUPANT LOAD AND REQUIRED SIZING FOR THE CORRIDOR |
| WIDTH AND STAIR WIDTH. PLEASE BE AWARE THE PROPOSED |
| PLAN NOW SHOWS ONLY TENANT 5 AS AN A-2 OCCUPANCY. IF |
| TENANTS 4,5, & 6 ALL CHANGE TO AN A2 OCCUPANCY THE |
| EXITING FOR THIS PORTION OF THE BUILDING WILL |
| DRASTICALLY CHANGE, WORST CASE SCENARIO!!!!!. * TENANT |
| SPACE MAY CHANGE PER FUTURE TENANT BUILDOUT OF SPACE. |
| |
| 1D) 3RD REQUEST. DEPENDING ON THE ABOVE CALCULATIONS |
| THE DOUBLE DOORS 03-B & 05-C MAY NEED TO BE RECESSED |
| BACK INTO THE TENANT SPACE TO NOT ENCROACH INTO THE |
| MEANS OF EGRESS SEE SECTION 1005.7.1 OF THE 2020 |
| FBC-BUILDING CODE. WORST CASE SCENARIO A-2 ASSEMBLY @ |
| 15 SQ. FT./ OCCUPANT. * TENANT SPACE MAY CHANGE PER |
| FUTURE TENANT BUILDOUT OF SPACE. |
| |
| 1E) 3RD REQUEST. SINCE TENANT 6 ALL OF THE OCCUPANT |
| LOAD NOW ENTERS INTO THE CORRIDOR 17, AND 2 MEANS OF |
| EGRESS OVER 1/3RD THE OVERALL DIAGONAL DISTANCE OF THE |
| TENANT SPACE AND THEY DO NOT CONVERGE ANOTHER MEANS OF |
| EGRESS IS REQUIRED (1007.1.1). THE DOORS ON THE RIGHT |
| SIDE OF THE PAGE WILL NEED TO SWING IN THE DIRECTION OF |
| EGRESS TRAVEL 1010.1.2.1 DIRECTION OF SWING, 2020 |
| FBC-BUILDING. |
| |
| 1F) 3RD REQUEST. COMMON DOORS BETWEEN TENANT # 6 AND |
| TENANT # 5, DOORS, 03-A, 04-A, 04-B, 05-A 05-B WILL |
| NEED TO SWING IN THE DIRECTION OF EGRESS TRAVEL AND |
| WILL NEED TO BE RECESSED INTO THE TENANT SPACE TO |
| MAINTAIN THE 44 INCH EGRESS PATH AS SHOWN ON THE PLAN. |
| CURRENTLY THE EGRESS PATH OF 44 INCHES(MERCANTILE) DOES |
| NOT NEED TO BE INCREASED, 44/ 0.2=220 OCCUPANTS. * |
| TENANT SPACE MAY CHANGE PER FUTURE TENANT BUILDOUT OF |
| SPACE. |
| |
| 1G) 3RD REQUEST. WEST SIDE OF TENANT SPACE DOOR 04-C |
| WOULD ALSO NEED TO BE REVERSED TO SWING IN THE |
| DIRECTION OF EGRESS TRAVEL AND MAY NEED TO BE RECESSED |
| DEPENDING ON THE CALCULATIONS FROM COMMENT 1C. |
| 1010.1.2.1 DIRECTION OF SWING, 2020 FBC-BUILDING. * |
| TENANT SPACE MAY CHANGE PER FUTURE TENANT BUILDOUT OF |
| SPACE. |
| |
| 1H) THERE ARE CONCERNS WITH THE OCCUPANT LOADS GOING |
| THROUGH DOORS 02-A & 02-B THE NEW OCCUPANT LOAD THAT |
| WILL BE GOING THROUGH THESE DOORS AS THE PLANS ARE |
| PROPOSED NOW WITH ONLY ONE A2 ASSEMBLY OCCUPANCY TENANT |
| SPACE 5. IF TENANT 4 & 6 BECOME AN A2 OCCUPANCY THE |
| OCCUPANT LOAD QUADRUPLES, THE TOTAL OCCUPANT LOAD FOR |
| SPACES 4, 5, 6 ALONE WOULD BE 881 OCCUPANTS REQUIRING A |
| 3RD EXIT AND THE CORRIDOR 17 WOULD NOT BE WIDE ENOUGH, |
| PLEASE BE AWARE OF ISSUE ISSUES!!!! . * TENANT SPACE |
| MAY CHANGE PER FUTURE TENANT BUILDOUT OF SPACE. |
| |
| 1I) 3RD REQUEST. PLEASE UPDATE THE OCCUPANT LOADS THAT |
| WILL BE EXITING THE BUILDING WITH THE REQUIRED CHANGES |
| WHERE TENANT 6, 5 & 4 WILL BE HAVING OF THEIR OCCUPANT |
| LOAD GOING DOWN THE STAIRS. * TENANT SPACE MAY CHANGE |
| PER FUTURE TENANT BUILDOUT OF SPACE. |
| 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION |
| DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1J) 3RD REQUEST. THE PROPOSED LIFE SAFETY SHEET NOR |
| A1-01 SHOW WHERE A GREASE TRAP IS TO BE LOCATED FOR THE |
| FUTURE KITCHEN. WHEN SPEAKING WITH MR. GATHRIGHT ASST. |
| B. O. WHEN FIRST MEETINGS WITH THE DESIGN TEAM IT WAS |
| ANNOUNCED THE GREASE TRAP COULD NOT BE LOCATED IN THE |
| CORRIDOR 17. 1003.4 FLOOR SURFACE. |
| |
| 2) 3RD REQUEST. THE CODE CAN NOT GIVE SECTIONS FOR ALL |
| SITUATIONS THAT OCCUR IN A BUILDING, WE USE THE |
| TERMINATION ROOM THAT IS MOST LIKE YOUR DESIGN. LIFE |
| SAFETY PLAN, A1-01, A0-01 ALL SHOW THE TRASH |
| TERMINATION ROOM AND ACCESS ROOM FOR TRASH DISPOSAL. |
| NONE OF THE PLANS SHOW THE TRASH TERMINATION ROOM AND |
| ACCESS ROOM WITH FIRE RATED WALLS SEPARATING THE |
| CORRIDOR 17 FROM THE TRASH TERMINATION ROOM IN |
| ACCORDANCE WITH 713.4 ONE HOUR ENCLOSURE WITH OPENING |
| PROTECTION IN ACCORDANCE WITH TABLE 716.5. |
| |
| 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |