Plan Review Notes
Plan Review Notes For Permit 22041143
Permit Number 22041143
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-23 17:35:281ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22041143
 5/23/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.01 & P PLANS: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR TENANT SPACE 2- TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES.
  
 2) P PLANS: PROVIDE A PLUMBING FIXTURE SCHEDULE- SEC.
 107.2.1 WPB.
  
 3) A1-01 & P PLANS- IDENTIFY THE TOILET ROOMS AS MALE,
 FEMALE OR UNISEX- SEC. 403.2 FBC P.
  
 4) A5-01 DETAIL 8: PROVIDE THE DIMENSIONS OF THE WATER
 CLOSET AND LAVATORY CLEAR FLOOR SPACE DIAGRAMS- SECS.
 604.3 & 606.2 FBC ACC.
  
 5) A5-01 DETAIL 7: PROVIDE THE HEIGHT OF THE WATER
 CLOSET SEAT FROM THE FINISHED FLOOR- SEC. 604.4 FBC
 ACC.
  
 6) A-5.01 DETAIL 4: PROVIDE THE DIMENSIONS OF THE WATER
 CLOSET AND LAVATORY CLEAR FLOOR SPACE DIAGRAMS- SECS.
 604.3 & 606.2 FBC ACC. IT APPEARS THAT THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET WILL BE UNDERSIZED AND NOT
 IN COMPLIANCE WITH SEC. 604.3 FBC ACC.
  
 7) P0-03 & P1.01: THE 1/2-INCH HW FIXTURE SUPPLY PIPES
 TO THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM 2FT.
 LENGTH FROM THE SOURCE OF HW- TABLE C404.5.1 FBC EC.
 PLEASE NOTE THE HWR LINE IS CONSIDERED A SOURCE OF HOT
 WATER.
  
 8) P0-03 & P1.01: PROVIDE THE MEANS OF DELIVERING
 TEMPERED WATER FROM THE LAVATORIES- SECS. 419.5 &
 606.1.2 FBC P.
  
 9) P0-03 & P1.01: A MEANS OF LIMITING THE HOT WATER
 DELIVERY TEMPERATURE AT FIXTURES IS REQUIRED AND CANNOT
 BE THE THERMOSTAT ON THE WATER HEATER. PLEASE PROVIDE A
 MASTER THERMOSTATIC MIXING VALVE OR POINT OF USE MIXING
 VALVES WHERE REQUIRED SUCH AS MOP OR KITCHEN SINKS AND
 DISHWASHERS. PLEASE DO CONFUSE THE REQUIREMENT WITH THE
 REQUIREMENT FOR TEMPERED WATER AT LAVATORIES. PLEASE
 SEE DEFINITIONS- SEC. 202.
  
 10) P1-R0: PLEASE PROVIDE A REVISED STORM DRAIN
 ISOMETRIC SHOWING THE ERD HORIZONTAL AND VERTICAL STORM
 DRAIN PIPE RUNS AND TERMINATION LOCATIONS- SEC. 1108.2
 FBC P. PLEASE NOTE THAT ROOF DRAINAGE FROM SCUPPERS,
 DOWNSPOUTS ETC.SHALL NOT FLOW ONTO ADJACENT PROPERTIES-
 SEC. 110.9 WPB IMPACT OF CONSTRUCTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  