2022-05-25 10:10:09 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. REVISION: 22041143 |
| W. P. B. PERMIT: 21051228 |
| ADD: 424 PRK PLACE |
| CONT: HEDRICK BROTHERS |
| TEL: 561-578-1602 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| PERMIT: 21051228 SHEET G0.04 CODE DATA: |
| AREA LIMITATIONS: A-2 OCCUPANCY, TYPE VB CONSTRUCTION, |
| FIRE SPRINKLERED |
| BUILDING OCCUPANCIES: A-2 RESTAURANT, M MERCANTILE, B |
| BUSINESS & S-2 BACK OF HOUSE STORAGE |
| |
| 1ST REVIEW REVISION: 22041143 TENANT BUILDOUT |
| DATE: WED. MAY 25TH/ 2022 |
| ACTION: DENIED |
| |
| |
| |
| 1) SHEET G1-01 LIFE SAFETY PLAN: |
| 1A) TENANT SPACE # 6 SHOWS ALL OF THE TENANTS EXITING |
| OUT OF THIS SPACE INTO CORRIDOR # 17. THE OCCUPANT LOAD |
| FOR THIS MERCANTILE OCCUPANCY IS 98 OCCUPANTS, PLUS ? |
| (57) OCCUPANTS OF THE OCCUPANT LOAD FROM TENANT SPACE 5 |
| IS ALSO EXITING THROUGH TENANT SPACE 6 THE WAY THE EXIT |
| DIRECTIONAL LIGHTS ARE POSITIONED AND DOOR SWING. 2010 |
| FBC-B SECTION 1006.2.1 & TABLE 1006.2.1. |
| |
| 1B) THE LIFE SAFETY SHEET DOES NOT PROVIDE DIMENSIONS |
| FOR EITHER PORTION OF CORRIDOR # 17. SHEET A1-01 |
| DIMENSIONS FROM THE EXTERIOR WALL TO THE INSIDE (TENANT |
| SIDE) OF THE CORRIDOR WALL TO DETERMINE CODE COMPLIANCE |
| FOR SIZING MEANS OF EGRESS. 2010 FBC-BUILDING SECTIONS |
| 1005.3.1 & 1005.3.2. |
| |
| 1C) THE CORRIDOR # 17 SERVES AS THE MEANS OF EGRESS AS |
| SHOWN FOR TENANT 4 (1/2 OF OCC. LOAD), TENANT 5 (1/2 OF |
| OCCUPANT LOAD) ALL OF TENANT 6 NEEDS TO CHANGE AND ALL |
| OF TENANT 7, PROVIDE THE TOTAL OCCUPANT LOAD AND |
| REQUIRED SIZING FOR THE CORRIDOR WIDTH AND STAIR WIDTH. |
| PLEASE BE AWARE THE PROPOSED PLAN NOW SHOWS ONLY TENANT |
| 5 AS AN A-2 OCCUPANCY. IF TENANTS 4,5, & 6 ALL CHANGE |
| TO AN A2 OCCUPANCY THE EXITING FOR THIS PORTION OF THE |
| BUILDING WILL DRASTICALLY CHANGE!!!!! |
| |
| 1D) DEPENDING ON THE ABOVE CALCULATIONS THE DOUBLE |
| DOORS 03-B & 05-C MAY NEED TO BE RECESSED BACK INTO THE |
| TENANT SPACE TO NOT ENCROACH INTO THE MEANS OF EGRESS |
| SEE SECTION 1005.7.1 OF THE 2020 FBC-BUILDING CODE. |
| |
| 1E) SINCE TENANT 6 ALL OF THE OCCUPANT LOAD NOW ENTERS |
| INTO THE CORRIDOR 17, AND 2 MEANS OF EGRESS OVER 1/3RD |
| THE OVERALL DIAGONAL DISTANCE OF THE TENANT SPACE AND |
| THEY DO NOT CONVERGE ANOTHER MEANS OF EGRESS IS |
| REQUIRED (1007.1.1). THE DOORS ON THE RIGHT SIDE OF THE |
| PAGE WILL NEED TO SWING IN THE DIRECTION OF EGRESS |
| TRAVEL 1010.1.2.1 DIRECTION OF SWING, 2020 |
| FBC-BUILDING. |
| |
| 1F) COMMON DOORS BETWEEN TENANT # 6 AND TENANT # 5, |
| DOORS, 03-A, 04-A, 04-B, 05-A 05-B WILL NEED TO SWING |
| IN THE DIRECTION OF EGRESS TRAVEL AND WILL NEED TO BE |
| RECESSED INTO THE TENANT SPACE TO MAINTAIN THE 44 INCH |
| EGRESS PATH AS SHOWN ON THE PLAN. CURRENTLY THE EGRESS |
| PATH OF 44 INCHES DOES NOT NEED TO BE INCREASED, 44/ |
| 0.2=220 OCCUPANTS. |
| |
| 1G) WEST SIDE OF TENANT SPACE DOOR 04-C WOULD ALSO NEED |
| TO BE REVERSED TO SWING IN THE DIRECTION OF EGRESS |
| TRAVEL AND MAY NEED TO BE RECESSED DEPENDING ON THE |
| CALCULATIONS FROM COMMENT 1C. 1010.1.2.1 DIRECTION OF |
| SWING, 2020 FBC-BUILDING. |
| |
| 1H) THERE ARE CONCERNS WITH THE OCCUPANT LOADS GOING |
| THROUGH DOORS 02-A & 02-B THE NEW OCCUPANT LOAD THAT |
| WILL BE GOING THROUGH THESE DOORS AS THE PLANS ARE |
| PROPOSED NOW WITH ONLY ONE A2 ASSEMBLY OCCUPANCY TENANT |
| SPACE 5. IF TENANT 4 & 6 BECOME AN A2 OCCUPANCY THE |
| OCCUPANT LOAD QUADRUPLES, THE TOTAL OCCUPANT LOAD FOR |
| SPACES 4, 5, 6 ALONE WOULD BE 881 OCCUPANTS REQUIRING A |
| 3RD EXIT AND THE CORRIDOR 17 WOULD NOT BE WIDE ENOUGH, |
| PLEASE BE AWARE OF ISSUE ISSUES!!!! |
| |
| 1I) PLEASE UPDATE THE OCCUPANT LOADS THAT WILL BE |
| EXITING THE BUILDING WITH THE REQUIRED CHANGES WHERE |
| TENANT 6, 5 & 4 WILL BE HAVING ? OF THERE OCCUPANT LOAD |
| GOING DOWN THE STAIRS. |
| 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION |
| DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1J) THE PROPOSED LIFE SAFETY SHEET NOR A1-01 SHOW WHERE |
| A GREASE TRAP IS TO BE LOCATED FOR THE FUTURE KITCHEN. |
| WHEN SPEAKING WITH MR. GATHRIGHT ASST. B. O. WHEN FIRST |
| MEETINGS WITH THE DESIGN TEAM IT WAS ANNOUNCED THE |
| GREASE TRAP COULD NOT BE LOCATED IN THE CORRIDOR 17. |
| 1003.4 FLOOR SURFACE. |
| |
| 2) LIFE SAFETY PLAN, A1-01, A0-01 ALL SHOW THE TRASH |
| TERMINATION ROOM AND ACCESS ROOM FOR TRASH DISPOSAL. |
| NONE OF THE PLANS SHOW THE TRASH TERMINATION ROOM AND |
| ACCESS ROOM WITH FIRE RATED WALLS SEPARATING THE |
| CORRIDOR 17 FROM THE TRASH TERMINATION ROOM IN |
| ACCORDANCE WITH 713.4 ONE HOUR ENCLOSURE WITH OPENING |
| PROTECTION IN ACCORDANCE WITH TABLE 716.5. |
| |
| 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |