2022-05-03 17:21:40 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22041026 |
| 5/3/22 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLUMBING PLANS SHALL BE DRAWN BY THE PLUMBING |
| CONTRACTOR OF RECORD OR A FL. LICENSED ENGINEER- |
| FLORIDA STATUTES 471.003(2) (H) & 471.015. CONTRACTOR |
| PLANS SHALL BEAR THE PRINTED NAME, LICENSE NUMBER, AND |
| SIGNATURE OF THE PLUMBING CONTRACTOR OF RECORD- SEC. |
| 107.2.1 WPB. |
| |
| 2) FAIR HOUSING COMPLIANCE: |
| |
| WPB BUILDING DEPT. RECORDS INDICATE THE RESIDENTIAL |
| UNITS AT THE STRAND- 255 EVERNIA ST. WERE DESIGNED AND |
| CONSTRUCTED IN ACCORDANCE WITH THE FAIR HOUSING DESIGN |
| ACT. THE PROPOSED BATH ALTERATIONS SHALL BE DESIGNED |
| AND CONSTRUCTED IN ACCORDANCE WITH THE FHDA MANUAL OR |
| THE FAIR HOUSING DESIGN GUIDELINES CONTAINED IN THE FBC |
| ACC. THE DESIGNER SHALL INDICATE COMPLIANCE WITH |
| SPECIFICATION TYPE A OR B AND THE DRAWINGS SHALL |
| REFLECT THE SPECIFICATION. PLEASE REFER TO PAGES 7.34- |
| 7.39 OF THE FHDA MANUAL FOR EXPLANATORY INFORMATION. |
| MASTER BATH SHOWER CONVERSION- FDHA. |
| PAGES 7.56- 7.59: PROVIDE THE INTERIOR FINISH |
| DIMENSIONS OF THE SHOWER- WIDTH AND DEPTH. |
| PAGES 7.56- 7.59: SHOW THE REQUIRED 30X48-INCH CLEAR |
| FLOOR SPACE PARALLEL APPROACH DIAGRAM FLUSH WITH THE |
| CONTROL SIDE WALL. |
| PAGES 7.56- 7.59: PROVIDE AN ELEVATION DETAIL SHOWING |
| THE SHOWER CONTROLS LOCATION, AND THE GRAB BAR AND SEAT |
| REINFORCEMENT DETAILS- PAGES- 6.12-6.13. SHOW THE |
| LENGTHS, WIDTHS AND HEIGHTS AND THE TYPE OF |
| REINFORCEMENT MATERIAL TO BE USED. SEE SEC 603.1 FBC B |
| FOR ALLOWABLE MATERIALS IN NON-COMBUSTIBLE BUILDINGS. |
| |
| PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| COPY OF THE FAIR HOUSING AFFIDAVIT. |
| |
| 3) PROVIDE A SHOWER PAN AND DRAIN DETAIL- SEC. 421.5.1- |
| 421.5.2.6 FBC P. SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE TWO-PIECE DRAIN. |
| |
| 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SHOWER |
| VALVE- SEC. 412.3 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |