2022-06-01 14:07:43 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22040982 |
| 6/1/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A4.22 DETAIL 1: SHOW THE CLEAR FLOOR SPACE |
| DIMENSIONS FOR THE WATER CLOSET AND LAVATORY- SECS. |
| 604.3 & 606.2 FBC ACC. PLEASE NOTE THAT THE DOOR SHALL |
| NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR THE |
| LAVATORY- SEC. 603.2.3 FBC ACC. |
| |
| 2) P0.1: THE BOARDROOM SINK FIXTURE DRAIN SHALL NOT |
| CONNECT INTO THE BATHROOM WET VENT, AND SHALL DISCHARGE |
| DOWNSTREAM OF THE VENT- SEC. 912.1 FBC P. |
| |
| 3) P2.1: INSTALLATION OF NEW DRAIN OUTLETS MAY REQUIRE |
| THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| WILL BE MET- SECTION 107.2.1 WPB. |
| |
| 4) P2.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR |
| SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND |
| APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |