Plan Review Notes
Plan Review Notes For Permit 22040982
Permit Number 22040982
Review Stop M
Sequence Number 1
Notes
Date Text
2022-05-27 16:38:41PROVIDE THE OUTDOOR AIT CALCULATIONS FOR THIS TENANT
 SPACE. FMC 403.3.1.1
  
 REVISE THE MECHANICAL PLAN TO SHOW THE CONDENSATE
 PIPING MATERIAL SIZE AND TERMINATION LOCATION. FMC 307
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER