2022-05-05 09:24:43 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 22040970 | | 5/5/22 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) P0.1: LOCATION OF THE REQUIRED DEDICATED SHUT OFF | | VALVE FOR THE IWH UNDER THE SINK NOT SHOWN- SEC 503.1 | | FBC P. | | | | 2) P0.1, A1.1: PUBLIC LAVATORY LABELING AT THE SINK | | DETAIL INCORRECT. ACCORDING TO THE PLANS THE SINKS ARE | | IN THE COFFEE AND WELLNESS ROOMS - SEC. 107.2.1 WPB. | | | | 3) P0.1: HOT WATER, NOT TEMPERED WATER IS REQUIRED AT | | THE SINKS. REMOVE THE TEMPERED WATER MIXING VALVE AND | | ALL REFERENCES TO TEMPERED WATER- SECS 419.5 AND | | 607.1.2 FBC P. PROVIDE A MIXING VALVE THAT WILL LIMIT | | THE HOT WATER TEMPERATURE IN ACCORDANCE WITH SEC. | | 607.1.1. | | | | 4) P0.1: PROVIDE EQUIPMENT SCHEDULES FOR THE WATER | | HEATERS ON THE PLANS AND SUBMIT MANUFACTURER?S | | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SEC. | | 502.1 FBC P. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|