Plan Review Notes
Plan Review Notes For Permit 22040970
Permit Number 22040970
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-05 09:24:431ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040970
 5/5/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P0.1: LOCATION OF THE REQUIRED DEDICATED SHUT OFF
 VALVE FOR THE IWH UNDER THE SINK NOT SHOWN- SEC 503.1
 FBC P.
  
 2) P0.1, A1.1: PUBLIC LAVATORY LABELING AT THE SINK
 DETAIL INCORRECT. ACCORDING TO THE PLANS THE SINKS ARE
 IN THE COFFEE AND WELLNESS ROOMS - SEC. 107.2.1 WPB.
  
 3) P0.1: HOT WATER, NOT TEMPERED WATER IS REQUIRED AT
 THE SINKS. REMOVE THE TEMPERED WATER MIXING VALVE AND
 ALL REFERENCES TO TEMPERED WATER- SECS 419.5 AND
 607.1.2 FBC P. PROVIDE A MIXING VALVE THAT WILL LIMIT
 THE HOT WATER TEMPERATURE IN ACCORDANCE WITH SEC.
 607.1.1.
  
 4) P0.1: PROVIDE EQUIPMENT SCHEDULES FOR THE WATER
 HEATERS ON THE PLANS AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS- SEC.
 502.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  