Plan Review Notes
Plan Review Notes For Permit 22040970
Permit Number 22040970
Review Stop M
Sequence Number 1
Notes
Date Text
2022-05-11 14:25:341ST REVIEW FMC
 PERMIT: 22040970
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DEMO SHEET SHOWS THIS WAS MORE LIKE AN OPEN
 OFFICE. SHOW THE UNITS AND DUCTWORK THAT CONDITIONS THE
 AIR FOR THESE NEW ROOMS AND TENANT SPACE. FBC 107.2.1
  
 2) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH
 USE OF SPACE AND THE OCCUPANCY CLASSIFICATION IN FMC
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER