Plan Review Notes For Permit 22040938 |
Permit Number |
22040938 |
|
Review Stop |
Z |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2023-05-09 12:05:04 | INSUFFICIENT | | | | 1) REPEAT COMMENT: THE SURVEY SHOWS THE POWER POLE THAT | | WILL SUPPLY THE UNDERGROUND POWER ON PRIVATE PROPERTY | | AND REQUIRING A CROSSING OF THE PRIVATE PROPERTY TO | | REACH THE HANDHOLE AT STA 0+00. IN ORDER FOR THE | | UNDERGROUND ELECTRIC TO CROSS PRIVATE PROPERTY, IT MUST | | BE LOCATED WITHIN A GENERAL UTILITY EASEMENT. THE | | SURVEY DOES NOT SHOW AN EASEMENT AT THIS LOCATION. IF | | THERE IS AN EASEMENT, IT MUST BE SHOWN ON THE SURVEY | | AND THE UNDERGROUND ELECTRIC MUST CLEARLY BE SHOWN IN | | THE EASEMENT. IF NO EASEMENT IS PRESENT, THE | | UNDERGROUND ELECTRIC MUST COME FROM AN ALTERNATIVE | | LOCATION. | | | | 2) REPEAT COMMENT: SHEET E201 DOES NOT SHOW A POLE THAT | | MEETS THE CITY'S STEALTH REQUIREMENTS. THE ORIGINAL | | SUBMITTAL SHOWED A COMPLIANT POLE DESIGN. SHEETS A201 | | AND A502 SHOW A COMPLIANT POLE. ALL PLANS MUST SHOW | | CITY COMPLIANT POLES. | | | | 3) THE POLE HEIGHT AND STYLE (SUBJECT TO THE CORRECTION | | OF SHEET E201) MEET CITY REQUIREMENTS. THE POLE COLOR | | AT THIS LOCATION IS CORRECTLY SHOWN AS RAL/RAYCAP 7042 | | TRAFFIC GREY A. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] | | |
|