Plan Review Notes
Plan Review Notes For Permit 22040938
Permit Number 22040938
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-05-26 17:32:02INSUFFICIENT
  
 1) THE TALLEST UTILITY POLE IN THE RIGHT-OF-WAY SHOWN
 ON THE SURVEY IS LISTED AT 31.6 FEET TALL. THE WIRELESS
 FACILITY SHOWN ON SHEET A201 IS 32 FEET IN HEIGHT,
 WHICH EXCEEDS THE ALLOWANCE LISTED IN SECTION
 94-411(G)(1) OF THE CITY CODE.
  
 2) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, SHOWING THE RIGHT-OF-WAY LINE AND THE EDGE OF
 THE SIDEWALK, WITH DIMENSIONS FOR THE FULL LENGTH OF
 THE UNDERGROUND POWER ROUTE SO THAT STAFF CAN VERIFY
 THAT IT IS WITHIN A RIGHT-OR-WAY AND DOES NOT CONFLICT
 WITH ANY UNDERGROUND FACILITIES, INCLUDING LANDSCAPE
 ROOT AREAS.
  
 3) THANK YOU FOR PROVIDING THE CROSS SECTION OF THE
 UNDERGROUND ELECTRIC BORE; HOWEVER, THE 2.5-FOOT DEPTH
 IS NOT SUFFICIENT DEPTH TO AVOID THE ROOT SYSTEMS FOR
 THE TREES THAT THE BORE GOES UNDER. AT LEAST 3-FOOT
 DEPTH IS REQUIRED. THE CROSS SECTION NEEDS TO INCLUDE
 THE UTILITIES THAT IT CROSSES AND THE POLE EMBEDMENTS
 TO VERIFY THAT IT HAS SUFFICIENT DEPTH TO AVOID THEM.
  
 4) THE POLE STYLE MEETS CITY REQUIREMENTS. THE POLE
 COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP 7042 TRAFFIC
 GREY A.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  