2022-05-26 17:32:02 | INSUFFICIENT | | | | 1) THE TALLEST UTILITY POLE IN THE RIGHT-OF-WAY SHOWN | | ON THE SURVEY IS LISTED AT 31.6 FEET TALL. THE WIRELESS | | FACILITY SHOWN ON SHEET A201 IS 32 FEET IN HEIGHT, | | WHICH EXCEEDS THE ALLOWANCE LISTED IN SECTION | | 94-411(G)(1) OF THE CITY CODE. | | | | 2) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED | | SURVEYOR, SHOWING THE RIGHT-OF-WAY LINE AND THE EDGE OF | | THE SIDEWALK, WITH DIMENSIONS FOR THE FULL LENGTH OF | | THE UNDERGROUND POWER ROUTE SO THAT STAFF CAN VERIFY | | THAT IT IS WITHIN A RIGHT-OR-WAY AND DOES NOT CONFLICT | | WITH ANY UNDERGROUND FACILITIES, INCLUDING LANDSCAPE | | ROOT AREAS. | | | | 3) THANK YOU FOR PROVIDING THE CROSS SECTION OF THE | | UNDERGROUND ELECTRIC BORE; HOWEVER, THE 2.5-FOOT DEPTH | | IS NOT SUFFICIENT DEPTH TO AVOID THE ROOT SYSTEMS FOR | | THE TREES THAT THE BORE GOES UNDER. AT LEAST 3-FOOT | | DEPTH IS REQUIRED. THE CROSS SECTION NEEDS TO INCLUDE | | THE UTILITIES THAT IT CROSSES AND THE POLE EMBEDMENTS | | TO VERIFY THAT IT HAS SUFFICIENT DEPTH TO AVOID THEM. | | | | 4) THE POLE STYLE MEETS CITY REQUIREMENTS. THE POLE | | COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP 7042 TRAFFIC | | GREY A. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | | | |
|