Plan Review Notes For Permit 22040922 |
Permit Number |
22040922 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-06-30 15:59:14 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 22040922 | | REVIEWED: JUNE 30, 2022 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER PX4191 | | [email protected] | | 561-805-6718 | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | BELOW) | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | BUILDING-PERMIT-FORMS | | FBC[B] = FBC BUILDING | | FBC[EXISTING] = FBC EXISTING BUILDING | | | | | | THE PRESSURE DESIGN WAS RECEIVED AND REVIEWED. | | IT STATES | | OPENING 1 DESIGN PRESSURES OF +66.4 AND -64.4 INTERIOR | | ZONE | | OPENING 2 AND 3 DESIGN PRESSURES +66.4 AND -121.8 | | EXTERIOR ZONE | | | | WITH THOSE DESIGN PRESSURES WE NOW NEED TO SEE THAT THE | | SELECTIONS MADE WILL EXCEED THOSE PRESSURES. | | SHEET 13 OF 20 IN PRODUCT APPROVAL SELECTS SPACING FOR | | -75 PRESSURE. | | | | PLEASE UPDATE YOUR SELECTION FOR OPENINGS 2 AND 3 TO | | MEET OR EXCEED -121.8 AS INDICATED AS DESIGN PRESSURE. | | | | ALSO, UPDATE THE INSTALLATION SCHEDULE TO SHOW THE | | DESIGN PRESSURES IN COLUMN 3. THEY SHOULD MATCH THE | | DESIGN PRESSURES FROM THE ENGINEER. | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | [email protected] | | |
|