2022-06-30 15:59:14BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 22040922
 REVIEWED: JUNE 30, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
  
  
 THE PRESSURE DESIGN WAS RECEIVED AND REVIEWED.
 IT STATES
 OPENING 1 DESIGN PRESSURES OF +66.4 AND -64.4 INTERIOR
 ZONE
 OPENING 2 AND 3 DESIGN PRESSURES +66.4 AND -121.8
 EXTERIOR ZONE
  
 WITH THOSE DESIGN PRESSURES WE NOW NEED TO SEE THAT THE
 SELECTIONS MADE WILL EXCEED THOSE PRESSURES.
 SHEET 13 OF 20 IN PRODUCT APPROVAL SELECTS SPACING FOR
 -75 PRESSURE.
  
 PLEASE UPDATE YOUR SELECTION FOR OPENINGS 2 AND 3 TO
 MEET OR EXCEED -121.8 AS INDICATED AS DESIGN PRESSURE.
  
 ALSO, UPDATE THE INSTALLATION SCHEDULE TO SHOW THE
 DESIGN PRESSURES IN COLUMN 3. THEY SHOULD MATCH THE
 DESIGN PRESSURES FROM THE ENGINEER.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  