Plan Review Notes
Plan Review Notes For Permit 22040922
Permit Number 22040922
Review Stop B
Sequence Number 2
Notes
Date Text
2022-06-11 08:37:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ONLY WIND LOAD ENGINEERING WAS SUBMITTED FOR 2ND REVIEW
  
 1. FBC B 1609, FS471, THE DESIGN PRESSURES SPECIFIED BY
 THE ENGINEER ARE HIGHER THAN THE DESIGN PRESURES THE
 CONTRACTOR USED TO SPECIFY FASTENING.
  
 EMAIL [email protected], REQUEST THAT THE
 DOCUMENT SE210555. LAVIA. DESIGN PRESSURE.PDF BE
 DELETED AS IT IS IN CONFLICT WITH THE ENGINEERING.
  
 SEE THE ENGINEERING PROVIDED. THE ENGINEER SPECIFIES:
  
 ZONE 4: +66.4/-66.4
 ZONE 5: +66.4/-121.8
  
 SEE THE FLOOR PLAN. THE WAY THAT THE DRAWING DEPICTS
 THE SHUTTERS, AT LEAST A PORTION IS IN ZONE 5.
 THEREFORE YOU NEED TO USE EITHER ZONE 5 PRESSURES OR
 HAVE THE ENGINEER SPECIFY DESIGN PRESSURES FOR EACH
 OPENING.
  
 OR, REDRAW THE PLAN SHOWING THE DISTANCE FROM THE
 CORNER TO THE EDGE OF THE SHUTTER.
  
 2. THE INSTALLATION SCHEDULE CANNOT BE REVIEWED UNTIL
 DESIGN PRESSURES ARE DETERMINED.
  