Plan Review Notes For Permit 22040917 |
Permit Number |
22040917 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-10 14:18:26 | ELECTRIC REVIEW FAILED | | 1) IT APPEARS THE LOAD CALCULATION SUBMITTED IS NOT FOR | | THIS SERVICE AS IT STATES A LOAD OF 132-AMPS FOR A | | 100-AMP SERVIC. PLEASE PROVIDE AN ACCURATE LOAD | | CALCULATION. NEC 215.5 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|