Plan Review Notes
Plan Review Notes For Permit 22040904
Permit Number 22040904
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-02 08:41:53JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL14317-R12 COVERS MULTIPLE PRODUCT TYPES;
 ROOF COVER OPTIONS; ALLOWABLE
 UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE
 SUBSTRATES & INSTALLATION METHODS. SELECT ALL
 APPLICABLE OPTIONS. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 2. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL
 LIMITATIONS #7 OF MIAMI-DADE NOA NO.: 20-0131.01.
 PLEASE NOTE THIS PROJECT IS LOCATED IN AN EXPOSURE C
 CATEGORY AREA.
 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW
 POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  