2022-07-05 12:48:03BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 2ND REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS
 THAT ARE LISTED ON THE DRAWINGS. MAKING SURE THAT THEY
 ARE THE CURRENT REVISION 14218- R7 HAS BEEN REVISED
 (14218 - R12)
  
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 HOLDER LOCATION DIMENSIONS FROM THE FACE OF THE TOILET
 AND FROM THE FLOOR FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS
  
  