Plan Review Notes For Permit 22040747 |
Permit Number |
22040747 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-05-31 11:59:05 | 2ND PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. DONE | | | | 2. 2020 FPC 607.1/607.1.1/607.1.2 - PLEASE DETAILS FOR | | HOT WATER DELIVERY AS WELL AS TEMPERED WATER DELIVERY | | THAT COMPLIES WITH 607.1. TEMPERED WATER DELIVERY MUST | | BE LIMITED BY A DEVICE THAT COMPLIES WITH ASSE 1070. A | | THERMOSTAT CONTOL ON THE WATER HEATER SHALL NOT SERVE | | AS THE TERMPERATURE LIMITING MEANS FOR HOT WATER | | DELIVERY. | | | | TEMPERED WATER SHALL BE LIMITED BY A DEVICE THAT MEETS | | ASSE 1070, THE DETAILS MUST BE SHOWN. | | | | HOT WATER CANNOT BE LIMITED BY THE THERMOSTAT ON THE | | WATER HEATER. A DEVICE MUST BE SHOWN. | | | | SIMPLY SETTING THE THERMOSTAT DOES NOT COMPLY WITH | | EITHER OF THESE REQUIREMENTS. | | | | 3. DONE | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|