Plan Review Notes For Permit 22040747
Permit Number 22040747
Review Stop P
Sequence Number 2
Notes
Date Text
2022-05-31 11:59:052ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. 2020 FPC 607.1/607.1.1/607.1.2 - PLEASE DETAILS FOR
 HOT WATER DELIVERY AS WELL AS TEMPERED WATER DELIVERY
 THAT COMPLIES WITH 607.1. TEMPERED WATER DELIVERY MUST
 BE LIMITED BY A DEVICE THAT COMPLIES WITH ASSE 1070. A
 THERMOSTAT CONTOL ON THE WATER HEATER SHALL NOT SERVE
 AS THE TERMPERATURE LIMITING MEANS FOR HOT WATER
 DELIVERY.
  
 TEMPERED WATER SHALL BE LIMITED BY A DEVICE THAT MEETS
 ASSE 1070, THE DETAILS MUST BE SHOWN.
  
 HOT WATER CANNOT BE LIMITED BY THE THERMOSTAT ON THE
 WATER HEATER. A DEVICE MUST BE SHOWN.
  
 SIMPLY SETTING THE THERMOSTAT DOES NOT COMPLY WITH
 EITHER OF THESE REQUIREMENTS.
  
 3. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  