Plan Review Notes For Permit 22040747 |
Permit Number |
22040747 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-06-06 14:56:09 | BUILD OUT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | 2ND REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS AND DOORS | | THAT ARE LISTED ON THE DRAWINGS. | | | | 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER | | HOLDER LOCATION DIMENSIONS FROM THE FACE OF THE TOILET | | AND FROM THE FLOOR FBC A 604.7 DISPENSERS. | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 | | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND | | SHALL NOT BE LOCATED BEHIND GRAB BARS | | | | |
|