Date Text
2022-04-27 09:29:211ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 #3,4 - MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS - PLEASE SHOW THE
 ISOMETRICS FOR THE WATER SUPPLY PIPING AND THE DRAIN,
 WASTE, AND VENT PIPING FOR YOUR INTENDED CONNECTION.
  
 2. 2020 FPC 607.1/607.1.1/607.1.2 - PLEASE DETAILS FOR
 HOT WATER DELIVERY AS WELL AS TEMPERED WATER DELIVERY
 THAT COMPLIES WITH 607.1. TEMPERED WATER DELIVERY MUST
 BE LIMITED BY A DEVICE THAT COMPLIES WITH ASSE 1070. A
 THERMOSTAT CONTOL ON THE WATER HEATER SHALL NOT SERVE
 AS THE TERMPERATURE LIMITING MEANS FOR HOT WATER
 DELIVERY.
  
 3. 2020 FPC 403.1 - PLEASE PROVIDE A SERVICE SINK AS
 REQUIRED BY 403.1 - MINIMUM NUMBER OF FIXTURES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  