2022-05-03 14:28:34 | 1ST REVIEW FMC |
| PERMIT: 22040747 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS FOR THE HEAT AND COOLING LOADS. FEC |
| C403.2.1 |
| |
| 2) HOW ARE THESE AC UNITS PRODUCING THE REQUIRED HEAT |
| FOR THIS TENANT SPACE? FMC 309.1 |
| |
| 3) PLEASE PROVIDE A ROOF DRAWING DETAILING THE |
| LOCATIONS OF THE CONDENSING UNITS. FBC 107.2.1 |
| |
| 3) SHEET M100: KEYNOTE 3 INDICATES THE CONDENSATE TO BE |
| ROUTED TO THE NEW MOP SINK. THE CONDENSATE CANNOT BE |
| DRAINED INTO THE SANITARY SEWER. WEST PALM BEACH |
| MUNICIPAL CODE SEC. 90-126: A) GENERALLY. USERS SHALL |
| NOT DISCHARGE POLLUTANTS INTO THE WWF UNLESS IN |
| ACCORDANCE WITH THIS ARTICLE. |
| (B) DISCHARGE PROHIBITIONS. NO USER SHALL DISCHARGE |
| INTO THE WWF ANY WASTE OR WASTEWATER WHICH MAY CAUSE |
| PASS THROUGH OR INTERFERE WITH THE OPERATION OR |
| PERFORMANCE OF THE WWF. NO USER SHALL DISCHARGE INTO |
| THE WWF OR ANY CONNECTED SYSTEM ANY WASTE OR WASTEWATER |
| CONTAINING ANY OF THE FOLLOWING: |
| (5) STORMWATER, SURFACE WATER, GROUNDWATER, ARTESIAN |
| WELL WATER, ROOF RUNOFF, SUBSURFACE DRAINAGE, SWIMMING |
| POOL DISCHARGES, UNCONTAMINATED COOLING WATER, |
| UNPOLLUTED INDUSTRIAL PROCESS WATERS, AIR CONDITIONING |
| CONDENSATE, UNLESS SPECIFICALLY AUTHORIZED BY THE CITY |
| IN WRITING. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |