Plan Review Notes For Permit 22040625 |
Permit Number |
22040625 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2022-08-29 10:15:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FROM PREVIOUS LIST, NOT ADDRESSED. | | | | 3. PROVIDE A SITE PLAN THAT SHOWS THE FOOTING RELATIVE | | TO THE PROPERTY LINE, FBC 107. | | | | NOT ADDRESSED. THE SITE PLAN GRAPHICALLY SHOWS THE WALL | | OVER THE PROPERTY LINE. FOOTER IS NOT ECCENTRIC SO THE | | WAY IT IS DESIGNED, THE FOOTER WILL BE INSTALLED ON | | CITY AND NEIGHBORING PROPERTY. | | | | SK-1 INCLUDES A "TYPICAL PRIVACY WALL SECTION" AND | | "SITE / SURVEY". THE SITE WALL DETAIL ON THE SITE PLAN | | IS NOT ECCENTRIC, GRAPHICALLY THE SITE PLAN SHOWS THE | | WALL SLIGHTLY OVER THE PROPERTY LINE. IF INSTALLED AS | | DRAWN THE FOOTER WILL ENCROACH THE PROPERTY LINE BY | | ABOUT A FOOT. THE PROPOSED IMPROVEMENT MUST BE | | INSTALLED ON THE SUBJECT PROPERTY. |
|