Date Text
2022-05-28 08:50:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED WALL.
 THE STRUCTURAL DETAIL IS TO INCLUDE WIND DESIGN
 CRITERIA. DETAIL IS TO SHOW ALL STUCCO (OR OTHER
 MATERIAL) AND PAINT PROPOSED.
  
 2ND REVIEW, NOT ADDRESSED. THE PLAN SHOWS A PROPOSED
 WALL BEING INSTALLED ON WHAT APPEARS TO BE A MONOLITHIC
 SLAB, CALLS THAT "EXISTING". PROVIE THE PERMIT NUMBER.
 WIND DESIGN CRITERIA NOT PROVIDED. PROVIDE CALCULATIONS
 TO SHOW THAT THE "EXISTING" SLAB IS ADEQUATE TO SUPPORT
 THE PROPOSED BLOCK WALL. WATERPROOFING/PAINT/STUCCO NOT
 SHOWN. IS NONE PROPOSED?
  
 2. FBC 107, THE PLAN IS TO INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN. CALCULATIONS MAY BE REQUIRED.
  
 NOT ADDRESSED.
  
 3. PROVIDE A SITE PLAN THAT SHOWS THE FOOTING RELATIVE
 TO THE PROPERTY LINE, FBC 107.
  
 NOT ADDRESSED. THE SITE PLAN GRAPHICALLY SHOWS THE WALL
 OVER THE PROPERTY LINE.
  
 4. DUE TO THE PROPOSED CONSTRUCTION AT THE CITY
 SIDEWALK, AN ENGINEERING REVIEW STOP HAS BEEN ADDED.
  
 5. THE WALL IS SHOWN AS CONTINUOUS. HOW WILL OCCUPANTS
 EXIT THE PROPERTY IN THE EVENT OF AN EMERGENCY? HOW
 WILL OCCUPANTS ACCESS THE PROPERTY? FBC 107. SCOPE OF
 WORK IS NOT CLEAR.
  