2022-07-06 08:46:071ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22040599
 7/6/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS G1 & G2: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE RANGE AND INDICATE HOW THE AIR WILL BE
 PROVIDED- REFER TO SECTION G2407.1 FBC RES.
  
 2) G1 & G2: INDICATE HOW MAKE UP AIR WILL BE PROVIDED
 FOR THE GAS DRYER- SECS. G2407.1 & G2439.5 FBC RES.
  
 3) G1 & G2: PLEASE SHOW THE GAS WATER HEATERS,
 GENERATOR, POOL HEATER, AND BBQ GRILL WILL BE INSTALLED
 ABOVE THE FLOOD ELEVATION HEIGHT- SEC. R322.1.6 FBC
 RES.
  
 4) G1 & G2: IT APPEARS THE BBQ GAS GRILL WILL BE
 INSTALLED UNDER COMBUSTIBLE ROOF CONSTRUCTION. PLEASE
 NOTE THAT TYPICAL INSTALLATION GUIDELINES FOR BBQ
 GRILLS PROHIBIT INSTALLATIONS UNDER COMBUSTIBLE ROOFS
 WITHOUT INSTALLATION OF EXHAUST HOODS AND EXHAUST
 DUCTS. PLEASE SUBMIT THE INSTALLATION MANUAL FOR THE
 GRILL- SEC. G2408.1 FBC RES.
  
 5) G1 & G2: PLEASE PLACE A NOTE ON THE PLAN TO INDICATE
 SEPARATE PERMITS ARE REQUIRED FOR INSTALLATIONS OF THE
 GAS GENERATOR AND POOL HEATER- SECS. 105.1 & 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  