Plan Review Notes
Plan Review Notes For Permit 22040599
Permit Number 22040599
Review Stop B
Sequence Number 2
Notes
Date Text
2022-07-06 08:44:37NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) SOIL REPORT PROVIDED NEEDS TO BE DIGITALLY SIGNED BY
 THE ENGINEER. SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED
 IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 2) SURVEY PROVIDED NEEDS TO SHOW THE FEMA BASE FLOOD
 ELEVATION NUMBER.
  
 3) PRODUCT APPROVAL FL 20468 R0 IS EXPIRED - PLEASE UP
 DATE THE DOOR PRODUCT APPROVAL.
  
 4) CLOPAY OVERHEAD GARAGE DOOR PRODUCT APPROVAL IS
 PROVIDED BUT NOT ON THE ARCHITECT'S PRODUCT APPROVAL
 LIST. PLEASE ADD TO LIST.
  
 5) PLEASE SHOW THE EQUIPMENT (AC, GENERATOR ETC.) PAD
 ELEVATIONS TO MEET FLOOD REQUIREMENTS FBC R322.1.6
  
 6) THE STRUCTURAL DRAWINGS SHOW THE LOWEST FLOOR
 ELEVATION AT 9.00 NGVD - THE ARCHITECTURAL DRAWINGS
 SHOW THE LOWEST FLOOR ELEVATION AT 9.00 NAVD - NAVD VS
 NGVD - PLEASE SHOW ALL ELEVATIONS USING NAVD.