Plan Review Notes For Permit 22040599 |
Permit Number |
22040599 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-07-06 08:44:37 | NEW SFR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) SOIL REPORT PROVIDED NEEDS TO BE DIGITALLY SIGNED BY | | THE ENGINEER. SIGNED AND SEALED DRAWINGS IN PROJECTDOX | | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED | | IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | | | 2) SURVEY PROVIDED NEEDS TO SHOW THE FEMA BASE FLOOD | | ELEVATION NUMBER. | | | | 3) PRODUCT APPROVAL FL 20468 R0 IS EXPIRED - PLEASE UP | | DATE THE DOOR PRODUCT APPROVAL. | | | | 4) CLOPAY OVERHEAD GARAGE DOOR PRODUCT APPROVAL IS | | PROVIDED BUT NOT ON THE ARCHITECT'S PRODUCT APPROVAL | | LIST. PLEASE ADD TO LIST. | | | | 5) PLEASE SHOW THE EQUIPMENT (AC, GENERATOR ETC.) PAD | | ELEVATIONS TO MEET FLOOD REQUIREMENTS FBC R322.1.6 | | | | 6) THE STRUCTURAL DRAWINGS SHOW THE LOWEST FLOOR | | ELEVATION AT 9.00 NGVD - THE ARCHITECTURAL DRAWINGS | | SHOW THE LOWEST FLOOR ELEVATION AT 9.00 NAVD - NAVD VS | | NGVD - PLEASE SHOW ALL ELEVATIONS USING NAVD. |
|