Date |
Text |
2022-06-06 10:48:52 | ROOFING PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: ROOFING PERMIT REQUIRED. |
| PERMITS - 105.1 REQUIRED. |
| |
| 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER |
| BARRIER PER FBC R905.1.1. |
| UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL |
| CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE |
| APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION |
| R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE. |
| |
| 2. DESIGNER SHALL SELECT ATTACHMENT METHOD FOR CLAY |
| TILE. IF TILE ADHESIVE AH-160 WILL BE USED, PROVIDE |
| PRODUCT APPROVALS. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 3. PROVIDE NOA OR PRODUCT APPROVAL FOR FLAT ROOF. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 4. PROVIDE A ROOF DRAINAGE PLAN. |
| R903.4ROOF DRAINAGE. |
| UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF |
| DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE |
| ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL |
| BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR |
| PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY |
| THE ROOF SLOPE AND CONTRIBUTING ROOF AREA. |
| |
| 5. PROVIDE OVERFLOW DRAINS. |
| R903.4.1OVERFLOW DRAINS AND SCUPPERS. |
| WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| VERTICAL LEADERS OR DOWN-SPOUTS OR WALL AND PARAPET |
| SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| OVERFLOW DRAINS SHALL DISCHARGE TO AN APPROVED LOCATION |
| AND SHALL NOT BE CONNECTED TO ROOF DRAIN LINES. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |