2022-06-06 10:48:52ROOFING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: ROOFING PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER
 BARRIER PER FBC R905.1.1.
 UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL
 CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE
 APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION
 R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE.
  
 2. DESIGNER SHALL SELECT ATTACHMENT METHOD FOR CLAY
 TILE. IF TILE ADHESIVE AH-160 WILL BE USED, PROVIDE
 PRODUCT APPROVALS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PROVIDE NOA OR PRODUCT APPROVAL FOR FLAT ROOF.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4. PROVIDE A ROOF DRAINAGE PLAN.
 R903.4ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF
 DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE
 ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL
 BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY
 THE ROOF SLOPE AND CONTRIBUTING ROOF AREA.
  
 5. PROVIDE OVERFLOW DRAINS.
 R903.4.1OVERFLOW DRAINS AND SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWN-SPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
 OVERFLOW DRAINS SHALL DISCHARGE TO AN APPROVED LOCATION
 AND SHALL NOT BE CONNECTED TO ROOF DRAIN LINES.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  