2023-04-07 17:58:24 | |
| 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22040505 |
| 4/7/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. THE ARCHITECT'S NARRATIVE |
| RESPONSES INDICATE THE CLASSIFICATION OF THE SOUTH |
| ROOFTOP POOL HAS BEEN CHANGED TO A PRIVATE RESIDENTIAL |
| POOL FOR THE PENTHOUSE APARTMENT HOWEVER THE PLANS DO |
| NOT APPEAR TO REFLECT THE CHANGE. I AM UNABLE TO LOCATE |
| ANY PLAN WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL |
| POOL FOR PENTHOUSE RESIDENT USE ONLY. THE REPEATED |
| STATEMENT IN THE NARRATIVE THAT THE POOL ENTRY IS |
| ACCESS CONTROLLED DOES NOT APPEAR RELEVANT TO POOL |
| CLASSSIFICATIONS AS DEFINED IN SECS. 454.1.1& 454.2.2 |
| FBC B. |
| FAILED 1ST REVIEW COMMENTS ARE LISTED BELOW WITH |
| ADDITIONAL NOTES. |
| |
| 1) FAILED. SHEET PL0.21: PLEASE PROVIDE A SITE UTILITY |
| PLAN FOR THE ROOF TOP POOL- SEC. 107.2.1 WPB. SHOW THE |
| POINTS OF CONNECTIONS TO WATER SUPPLY LINE, WASTE AND |
| STORM DRAIN LINES, GAS PIPING, AND ELECTRICAL SERVICE. |
| PLEASE NOTE THAT THE WATER SUPPLY TO THE POOL SHALL BE |
| PROTECTED AGAINST BACKFLOW WITH AN RPZ TYPE BACKFLOW |
| PREVENTER WHICH SHALL BE INSTALLED UNDER A SEPARATE |
| PERMIT. SHOW THE LOCATION OF THE DEVICE AND PROVIDE |
| NOTES TO INDICATE COMPLIANCE- SEC. 105.1, 107.2.1 WPB, |
| AND WPB UTILITIES CROSS-CONNECTION MANUAL. |
| THE ARCHITECT'S NARRATIVE REFERENCES SHEET P5.03S AND |
| SS/19 FOR POOL BACKWASH INTO FUNNEL DRAIN. PLEASE NOTE |
| THE DRAINAGE SHALL NOT DISCHARGE INTO THE SANITARY |
| SEWER- SEC. 90-126 (5) WPB CODE OF ORDINANCES. |
| |
| 2) FAILED. PL0.21: PROVIDE PLUMBING FIXTURE |
| CALCULATIONS FOR THE POOL AND SHOW THE LOCATIONS OF THE |
| SANITARY FACILITIES- TABLE 454.1.6.1 AND SECS. |
| 454.1.6.1- 454.6.1.2 FBC B. IF CLAIMING THE EXCEPTION |
| UNDER SEC. 454.1.6.1 PLEASE PROVIDE NOTES AND DETAILS |
| ON THE PLAN TO VERIFY COMPLIANCE. THE SUBMITTED PLANS |
| DO NOT CLEARLY INDICATE THE LOCATIONS OF THE POOL |
| BATHROOMS AND WHICH BATHROOMS ARE DESIGNATED FOR USERS |
| OF THE POOL AND DECK AREAS. PROVIDE COMPLIANCE DETAILS |
| AND INFORMATION AS REQUIRED BY SECS. 454.1.6.1.1- |
| 454.1.6.1.4 FBC B. PLEASE NOTE THE REQUIRED SANITARY |
| FACILITIES AND PLUMBING FIXTURES REQUIRED FOR THE POOL |
| AREA (BATHROOM FIXTURES, HOSE BIBS, POOL SHOWERS) AND |
| IN THE EQUIPMENT ROOM- SHALL BE INSTALLED UNDER |
| SEPARATE PERMITS- SECS. 105.1 & 107.2.1 WPB. |
| THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS |
| FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO |
| REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN |
| WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR |
| PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS, |
| SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE |
| POOL- SEE SECS. 454.2, 454.2.2 FBC B. |
| |
| |
| 5) FAILED. SHEET PL2.00: INDICATE THE BATHING LOAD TO |
| BE BASED ON TRANSIENT OR NON-TRANSIENT USE- SEC. |
| 454.1.1.1 FBC B. |
| THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS |
| FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO |
| REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN |
| WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR |
| PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS, |
| SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE |
| POOL- SEE SECS. 454.2, 454.2.2 FBC B. |
| |
| |
| 7) FAILED. PL2.15 & PL2.30: THE WASTE WATER FROM THE |
| POOL VIA THE SUMP PUMP IN THE EQUIPMENT ROOM SHALL NOT |
| DRAIN INTO THE SANITARY SYSTEM. WASTEWATER FROM THE |
| POOL AND THE POOL EQUIPMENT SHALL BE DECHLORINATED AND |
| DISCHARGED THROUGH AN AIR GAP IN THE INTO THE STORM |
| DRAINAGE SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB |
| CODE OF ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE |
| INTO THE SANITARY SYSTEM. PLEASE REVIEW WPB BUILDING |
| DEPT. GUIDELINES FOR POOL WATER DISPOSAL. THE ENGINEER |
| OF RECORD SHALL SHOW THE DECHLORINATION SYSTEM ON THE |
| PLAN AND PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. |
| PLEASE SEE GUIDELINES BELOW- |
| |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL |
| OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, |
| PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| THE ARCHITECT'S RESPONSE REFERENCES SHEET P2.07S FOR |
| POOL WASTEWATER RECEIVING LOCATION. NOTES 12 & 14 |
| INDICATE FUNNEL DRAINS FOR POOL BACKWASH. PLEASE SHOW |
| DISPOSAL LOCATION OF THE BACKWASH- SANITARY OR STORM, |
| AND PLEASE IDENTIFY ALL OTHER DRAINS CONVEYING POOL |
| WASTEWATER AND THEIR RESPECTIVE DISPOSAL LOCATIONS. |
| |
| 8) FAILED. PL2.10: A WALL INLET IS REQUIRED DIRECTLY |
| ACROSS FROM THE SKIMMER- SEC. 454.1.6.5.3.2.4 FBC B. |
| THE ARCHITECT???S NARRATIVE INDICATES THE ROOFTOP POOL |
| IS FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO |
| REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN |
| WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR |
| PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS, |
| SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE |
| POOL- SEE SECS. 454.2, 454.2.2 FBC B. |
| |
| 9) FAILED. PL2.10: THE SPACING OF THE WALL INLETS DOES |
| NOT APPEAR TO BE IN COMPLIANCE WITH SEC. 454.1.6.5.9.1 |
| FBC B- SPACING SHALL NOT EXCEED 20 FT. |
| THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS |
| FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO |
| REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN |
| WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR |
| PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS, |
| SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE |
| POOL- SEE SECS. 454.2, 454.2.2 FBC B. |
| |
| 10) FAILED. PL2.15 SYSTEM DESIGN: PLEASE VERIFY THAT |
| THE DESIGN PATTERN OF THE RECIRCULATION FLOW SHALL BE |
| 100% THROUGH THE MAIN DRAIN PIPING, AND 60% THROUGH THE |
| SKIMMER SYSTEM- SEC. 454.1.6.5.3 FBC B. |
| THERE WAS NO PLAN NOTE OR DETAIL REFERENCED IN THE |
| RESPONSE TO CONFIRM COMPLIANCE. |
| |