Plan Review Notes
Plan Review Notes For Permit 22040505
Permit Number 22040505
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-07 17:58:24 
 2ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22040505
 4/7/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE ARCHITECT'S NARRATIVE
 RESPONSES INDICATE THE CLASSIFICATION OF THE SOUTH
 ROOFTOP POOL HAS BEEN CHANGED TO A PRIVATE RESIDENTIAL
 POOL FOR THE PENTHOUSE APARTMENT HOWEVER THE PLANS DO
 NOT APPEAR TO REFLECT THE CHANGE. I AM UNABLE TO LOCATE
 ANY PLAN WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL
 POOL FOR PENTHOUSE RESIDENT USE ONLY. THE REPEATED
 STATEMENT IN THE NARRATIVE THAT THE POOL ENTRY IS
 ACCESS CONTROLLED DOES NOT APPEAR RELEVANT TO POOL
 CLASSSIFICATIONS AS DEFINED IN SECS. 454.1.1& 454.2.2
 FBC B.
 FAILED 1ST REVIEW COMMENTS ARE LISTED BELOW WITH
 ADDITIONAL NOTES.
  
 1) FAILED. SHEET PL0.21: PLEASE PROVIDE A SITE UTILITY
 PLAN FOR THE ROOF TOP POOL- SEC. 107.2.1 WPB. SHOW THE
 POINTS OF CONNECTIONS TO WATER SUPPLY LINE, WASTE AND
 STORM DRAIN LINES, GAS PIPING, AND ELECTRICAL SERVICE.
 PLEASE NOTE THAT THE WATER SUPPLY TO THE POOL SHALL BE
 PROTECTED AGAINST BACKFLOW WITH AN RPZ TYPE BACKFLOW
 PREVENTER WHICH SHALL BE INSTALLED UNDER A SEPARATE
 PERMIT. SHOW THE LOCATION OF THE DEVICE AND PROVIDE
 NOTES TO INDICATE COMPLIANCE- SEC. 105.1, 107.2.1 WPB,
 AND WPB UTILITIES CROSS-CONNECTION MANUAL.
 THE ARCHITECT'S NARRATIVE REFERENCES SHEET P5.03S AND
 SS/19 FOR POOL BACKWASH INTO FUNNEL DRAIN. PLEASE NOTE
 THE DRAINAGE SHALL NOT DISCHARGE INTO THE SANITARY
 SEWER- SEC. 90-126 (5) WPB CODE OF ORDINANCES.
  
 2) FAILED. PL0.21: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE POOL AND SHOW THE LOCATIONS OF THE
 SANITARY FACILITIES- TABLE 454.1.6.1 AND SECS.
 454.1.6.1- 454.6.1.2 FBC B. IF CLAIMING THE EXCEPTION
 UNDER SEC. 454.1.6.1 PLEASE PROVIDE NOTES AND DETAILS
 ON THE PLAN TO VERIFY COMPLIANCE. THE SUBMITTED PLANS
 DO NOT CLEARLY INDICATE THE LOCATIONS OF THE POOL
 BATHROOMS AND WHICH BATHROOMS ARE DESIGNATED FOR USERS
 OF THE POOL AND DECK AREAS. PROVIDE COMPLIANCE DETAILS
 AND INFORMATION AS REQUIRED BY SECS. 454.1.6.1.1-
 454.1.6.1.4 FBC B. PLEASE NOTE THE REQUIRED SANITARY
 FACILITIES AND PLUMBING FIXTURES REQUIRED FOR THE POOL
 AREA (BATHROOM FIXTURES, HOSE BIBS, POOL SHOWERS) AND
 IN THE EQUIPMENT ROOM- SHALL BE INSTALLED UNDER
 SEPARATE PERMITS- SECS. 105.1 & 107.2.1 WPB.
 THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS
 FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO
 REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN
 WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR
 PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS,
 SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE
 POOL- SEE SECS. 454.2, 454.2.2 FBC B.
  
  
 5) FAILED. SHEET PL2.00: INDICATE THE BATHING LOAD TO
 BE BASED ON TRANSIENT OR NON-TRANSIENT USE- SEC.
 454.1.1.1 FBC B.
 THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS
 FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO
 REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN
 WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR
 PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS,
 SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE
 POOL- SEE SECS. 454.2, 454.2.2 FBC B.
  
  
 7) FAILED. PL2.15 & PL2.30: THE WASTE WATER FROM THE
 POOL VIA THE SUMP PUMP IN THE EQUIPMENT ROOM SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM. WASTEWATER FROM THE
 POOL AND THE POOL EQUIPMENT SHALL BE DECHLORINATED AND
 DISCHARGED THROUGH AN AIR GAP IN THE INTO THE STORM
 DRAINAGE SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB
 CODE OF ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE
 INTO THE SANITARY SYSTEM. PLEASE REVIEW WPB BUILDING
 DEPT. GUIDELINES FOR POOL WATER DISPOSAL. THE ENGINEER
 OF RECORD SHALL SHOW THE DECHLORINATION SYSTEM ON THE
 PLAN AND PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT.
 PLEASE SEE GUIDELINES BELOW-
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 THE ARCHITECT'S RESPONSE REFERENCES SHEET P2.07S FOR
 POOL WASTEWATER RECEIVING LOCATION. NOTES 12 & 14
 INDICATE FUNNEL DRAINS FOR POOL BACKWASH. PLEASE SHOW
 DISPOSAL LOCATION OF THE BACKWASH- SANITARY OR STORM,
 AND PLEASE IDENTIFY ALL OTHER DRAINS CONVEYING POOL
 WASTEWATER AND THEIR RESPECTIVE DISPOSAL LOCATIONS.
  
 8) FAILED. PL2.10: A WALL INLET IS REQUIRED DIRECTLY
 ACROSS FROM THE SKIMMER- SEC. 454.1.6.5.3.2.4 FBC B.
 THE ARCHITECT???S NARRATIVE INDICATES THE ROOFTOP POOL
 IS FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO
 REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN
 WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR
 PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS,
 SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE
 POOL- SEE SECS. 454.2, 454.2.2 FBC B.
  
 9) FAILED. PL2.10: THE SPACING OF THE WALL INLETS DOES
 NOT APPEAR TO BE IN COMPLIANCE WITH SEC. 454.1.6.5.9.1
 FBC B- SPACING SHALL NOT EXCEED 20 FT.
 THE ARCHITECT'S NARRATIVE INDICATES THE ROOFTOP POOL IS
 FOR PRIVATE USE HOWEVER THE PLANS DO NOT APPEAR TO
 REFLECT THE CHANGE. I AM UNABLE TO LOCATE ANY PLAN
 WHICH LABELS THE POOL AS A PRIVATE RESIDENTIAL POOL FOR
 PENTHOUSE RESIDENT USE ONLY. ALL NOTES, DETAILS,
 SPECIFICATIONS, ETC. INDICATE A COMMERCIAL, PUBLIC USE
 POOL- SEE SECS. 454.2, 454.2.2 FBC B.
  
 10) FAILED. PL2.15 SYSTEM DESIGN: PLEASE VERIFY THAT
 THE DESIGN PATTERN OF THE RECIRCULATION FLOW SHALL BE
 100% THROUGH THE MAIN DRAIN PIPING, AND 60% THROUGH THE
 SKIMMER SYSTEM- SEC. 454.1.6.5.3 FBC B.
 THERE WAS NO PLAN NOTE OR DETAIL REFERENCED IN THE
 RESPONSE TO CONFIRM COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  