2022-05-03 11:46:26 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22040505 |
| 5/3/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET PL0.21: PLEASE PROVIDE A SITE UTILITY PLAN FOR |
| THE ROOF TOP POOL- SEC. 107.2.1 WPB. SHOW THE POINTS OF |
| CONNECTIONS TO WATER SUPPLY LINE, WASTE AND STORM DRAIN |
| LINES, GAS PIPING, AND ELECTRICAL SERVICE. PLEASE NOTE |
| THAT THE WATER SUPPLY TO THE POOL SHALL BE PROTECTED |
| AGAINST BACKFLOW WITH AN RPZ TYPE BACKFLOW PREVENTER |
| WHICH SHALL BE INSTALLED UNDER A SEPARATE PERMIT. SHOW |
| THE LOCATION OF THE DEVICE AND PROVIDE NOTES TO |
| INDICATE COMPLIANCE- SEC. 105.1, 107.2.1 WPB, AND WPB |
| UTILITIES CROSS-CONNECTION MANUAL. |
| |
| 2) PL0.21: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR |
| THE POOL AND SHOW THE LOCATIONS OF THE SANITARY |
| FACILITIES- TABLE 454.1.6.1 AND SECS. 454.1.6.1- |
| 454.6.1.2 FBC B. IF CLAIMING THE EXCEPTION UNDER SEC. |
| 454.1.6.1 PLEASE PROVIDE NOTES AND DETAILS ON THE PLAN |
| TO VERIFY COMPLIANCE. THE SUBMITTED PLANS DO NOT |
| CLEARLY INDICATE THE LOCATIONS OF THE POOL BATHROOMS |
| AND WHICH BATHROOMS ARE DESIGNATED FOR USERS OF THE |
| POOL AND DECK AREAS. PROVIDE COMPLIANCE DETAILS AND |
| INFORMATION AS REQUIRED BY SECS. 454.1.6.1.1- |
| 454.1.6.1.4 FBC B. PLEASE NOTE THE REQUIRED SANITARY |
| FACILITIES AND PLUMBING FIXTURES REQUIRED FOR THE POOL |
| AREA (BATHROOM FIXTURES, HOSE BIBS, POOL SHOWERS) AND |
| IN THE EQUIPMENT ROOM- SHALL BE INSTALLED UNDER |
| SEPARATE PERMITS- SECS. 105.1 & 107.2.1 WPB. |
| |
| 3) PL0.21: PROVIDE A HOSE BIB ON THE POOL DECK AND |
| INCLUDE PIPING DETAILS AND AN EQUIPMENT SCHEDULE- SEC. |
| 454.1.3.1.5 FBC B. |
| |
| 4) PL0.21; PROVIDE AN ENLARGED POOL SHOWER SHOWING THE |
| TYPE OF VALVE, VALVE AND SHOWER HEAD HEIGHTS FROM THE |
| FINISHED FLOOR, AND SHOWER DRAINAGE LOCATION- SEC. |
| 107.2.1 WPB AND REQUIREMENT 2 FAIR HOUSING DESIGN |
| GUIDELINES-FBC ACC. |
| |
| 5) SHEET PL2.00: INDICATE THE BATHING LOAD TO BE BASED |
| ON TRANSIENT OR NON-TRANSIENT USE- SEC. 454.1.1.1 FBC |
| B. |
| |
| 6) PL2.00 & PL2.05: THE POOL DEPTH SHALL BE 4 FT. IN |
| THE DEEP AREA- SEC. 454.1.2.2.4 FBC B. |
| |
| 7) PL2.15 & PL2.30: THE WASTE WATER FROM THE POOL VIA |
| THE SUMP PUMP IN THE EQUIPMENT ROOM SHALL NOT DRAIN |
| INTO THE SANITARY SYSTEM. WASTEWATER FROM THE POOL AND |
| THE POOL EQUIPMENT SHALL BE DECHLORINATED AND |
| DISCHARGED THROUGH AN AIR GAP IN THE INTO THE STORM |
| DRAINAGE SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB |
| CODE OF ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE |
| INTO THE SANITARY SYSTEM. PLEASE REVIEW WPB BUILDING |
| DEPT. GUIDELINES FOR POOL WATER DISPOSAL. THE ENGINEER |
| OF RECORD SHALL SHOW THE DECHLORINATION SYSTEM ON THE |
| PLAN AND PROVIDE SPECIFICATIONS FOR ALL EQUIPMENT. |
| PLEASE SEE GUIDELINES BELOW- |
| |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL |
| OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, |
| PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 8) PL2.10: A WALL INLET IS REQUIRED DIRECTLY ACROSS |
| FROM THE SKIMMER- SEC. 454.1.6.5.3.2.4 FBC B. |
| |
| 9) PL2.10: THE SPACING OF THE WALL INLETS DOES NOT |
| APPEAR TO BE IN COMPLIANCE WITH SEC. 454.1.6.5.9.1 FBC |
| B- SPACING SHALL NOT EXCEED 20 FT. |
| |
| 10) PL2.15 SYSTEM DESIGN: PLEASE VERIFY THAT THE DESIGN |
| PATTERN OF THE RECIRCULATION FLOW SHALL BE 100% THROUGH |
| THE MAIN DRAIN PIPING, AND 60% THROUGH THE SKIMMER |
| SYSTEM- SEC. 454.1.6.5.3 FBC B. |
| |
| 11) PL2.15: SHOW THE LOCATION OF THE AUTO FILL AT THE |
| COLLECTOR TANK- SEC. 454.1.6.5.11 FBC B. |
| |
| 12) PL2.30: A HOSE BIB WITH A VACUUM BREAKER SHALL BE |
| INSTALLED IN THE EQUIPMENT ROOM- SEC. 454.1.5.9 FBC B. |
| PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR |
| INSTALLATION OF THE POOL HEATER AND GAS PIPING- |
| SEC.105.1 WPB. |
| |
| 13) PL.2.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| THE WALL RETURN FITTINGS, MAIN DRAIN ASSEMBLIES, |
| SKIMMER, THE ADA LIFT, AND THE EQUALIZER ASSEMBLY- SEC. |
| 107.2.1 WPB. |
| |
| 14) PL2.30: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| RECIRCULATION EQUIPMENT LISTED IN THE SCHEDULE- SEC. |
| 107.2.1 WPB. |
| |
| 15) PL0.22 POOL LIFT: PLEASE PROVIDE ENLARGED |
| DIMENSIONED DETAILS ON THE PLANS AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL |
| FOR THE LIFT- SEC.107.2.1 WPB.. SHOW COMPLIANCE WITH |
| THE FOLLOWING FBC ACC CODE SECTIONS: |
| A) 1009.2.2 SEAT LOCATION. |
| IN THE RAISED POSITION, THE CENTERLINE OF THE SEAT |
| SHALL BE LOCATED OVER THE DECK AND 16 INCHES MINIMUM |
| FROM THE EDGE OF THE POOL. THE DECK SURFACE BETWEEN THE |
| CENTERLINE OF THE SEAT AND THE POOL EDGE SHALL HAVE A |
| SLOPE NOT STEEPER THAN 1:48. |
| B) 1009.2.3 CLEAR DECK SPACE. |
| ON THE SIDE OF THE SEAT OPPOSITE THE WATER, A CLEAR |
| DECK SPACE SHALL BE PROVIDED PARALLEL WITH THE SEAT. |
| THE SPACE SHALL BE 36 INCHES WIDE MINIMUM AND SHALL |
| EXTEND FORWARD 48 INCHES MINIMUM FROM A LINE LOCATED 12 |
| INCHES BEHIND THE REAR EDGE OF THE SEAT. THE CLEAR DECK |
| SPACE SHALL HAVE A SLOPE NOT STEEPER THAN 1:48. |
| C) 1009.2.4 SEAT HEIGHT. |
| THE HEIGHT OF THE LIFT SEAT SHALL BE DESIGNED TO ALLOW |
| A STOP AT 16 INCHES MINIMUM TO 19 INCHES MAXIMUM |
| MEASURED FROM THE DECK TO THE TOP OF THE SEAT SURFACE |
| WHEN IN THE RAISED (LOAD) POSITION. |
| D) 1009.2.6 FOOTRESTS AND ARMRESTS. |
| FOOTRESTS SHALL BE PROVIDED AND SHALL MOVE WITH THE |
| SEAT. IF PROVIDED, THE ARMREST POSITIONED OPPOSITE THE |
| WATER SHALL BE REMOVABLE OR SHALL FOLD CLEAR OF THE |
| SEAT WHEN THE SEAT IS IN THE RAISED (LOAD) POS |
| E) 1009.2.7 OPERATION. |
| THE LIFT SHALL BE CAPABLE OF UNASSISTED OPERATION FROM |
| BOTH THE DECK AND WATER LEVELS. CONTROLS AND OPERATING |
| MECHANISMS SHALL BE UNOBSTRUCTED WHEN THE LIFT IS IN |
| USE AND SHALL COMPLY WITH 309.4. |
| F) 1009.2.8 SUBMERGED DEPTH. |
| THE LIFT SHALL BE DESIGNED SO THAT THE SEAT WILL |
| SUBMERGE TO A WATER DEPTH OF 18 INCHES MINIMUM BELOW |
| THE STATIONARY WATER LEVEL. |
| G) 1009.2.9 LIFTING CAPACITY. |
| SINGLE PERSON POOL LIFTS SHALL HAVE A WEIGHT CAPACITY |
| OF 300 POUNDS MINIMUM AND BE CAPABLE OF SUSTAINING A |
| STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED |
| LOAD. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |