Plan Review Notes
Plan Review Notes For Permit 22040505
Permit Number 22040505
Review Stop B
Sequence Number 1
Notes
Date Text
2022-06-23 12:13:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SITE SHOWN ON THE COVER SHEET PL0.00 IS NOT THE
 LOCATION OF THIS PROJECT. THIS PROJECT IS LOCATED AT
 4334 N. FLAGLER DRIVE, WEST PALM BEACH, FLORIDA, FBC
 AMENDMENTS 107.2.1
  
 2) SUBMIT A COPY OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE ADA POOL LIFT.
 FBC 107.2.1
  
 3) POOL IS SHOWN WITH A WATER DEPTH OF LESS THAN 4
 FEET. FBC 454.1.2.2.4 POOL DEPTHS. THE MINIMUM WATER
 DEPTH SHALL BE 3 FEET (914 MM) IN SHALLOW AREAS AND 4
 FEET (1219 MM) IN DEEP AREAS.
  
 4) SHOW THAT THERE IS ADEQUATE CLEARANCE AT THE POOL
 LIFT. FBC 454.1.2.5.6 DISABLED ACCESS. PERMANENT OR
 PORTABLE STEPS, RAMPS, HANDRAILS, LIFTS OR OTHER
 DEVICES DESIGNED TO ACCOMMODATE HANDICAPPED INDIVIDUALS
 IN SWIMMING POOLS MAY BE PROVIDED. LIFTS MOUNTED INTO
 THE POOL DECK SHALL HAVE A MINIMUM 4-FOOT-WIDE (1219
 MM) DECK BEHIND THE LIFT MOUNT.
  
 5) SHOW COMPLIANCE WITH FBC 454.1.3.1.3. POOL WET DECKS
 SHALL HAVE A MINIMUM UNOBSTRUCTED WIDTH OF 4 FEET (1219
 MM) AROUND THE PERIMETER OF THE POOL, POOL CURB,
 LADDERS, HANDRAILS, DIVING BOARDS, DIVING TOWERS AND
 SLIDES.
  
 6) SHOW COMPLIANCE WITH FBC 454.1.3.1.5. WALKWAYS SHALL
 BE PROVIDED BETWEEN THE POOL AND THE SANITARY
 FACILITIES, AND SHALL BE CONSTRUCTED OF CONCRETE OR
 OTHER NONABSORBENT MATERIAL HAVING A SMOOTH
 SLIP-RESISTANT FINISH FOR THE FIRST 15 FEET (4572 MM)
 OF THE WALKWAY MEASURED FROM THE NEAREST POOL WATER'S
 EDGE. A HOSE BIBB WITH A VACUUM BREAKER SHALL BE
 PROVIDED TO ALLOW THE DECK TO BE WASHED DOWN WITH
 POTABLE WATER.
  
 7) SHOW COMPLIANCE WITH FBC 454.1.6.1 SANITARY
 FACILITIES. SWIMMING POOLS WITH A BATHING LOAD OF 20
 PERSONS OR LESS MAY UTILIZE A UNISEX RESTROOM. POOLS
 WITH BATHING LOADS OF 40 PERSONS OR LESS MAY UTILIZE
 TWO UNISEX RESTROOMS OR MEET THE REQUIREMENTS OF TABLE
 454.1.6.1. UNISEX RESTROOMS SHALL MEET ALL THE
 REQUIREMENTS FOR MATERIALS, DRAINAGE AND SIGNAGE AS
 INDICATED IN SECTIONS 454.1.6.1.1 THROUGH 454.1.6.1.4.
 EACH SHALL INCLUDE A WATER CLOSET, A DIAPER CHANGE
 TABLE, A URINAL AND A LAVATORY. POOLS WITH A BATHING
 LOAD LARGER THAN 40 PERSONS SHALL PROVIDE SEPARATE
 SANITARY FACILITIES LABELED FOR EACH SEX. THE ENTRY
 DOORS OF ALL RESTROOMS SHALL BE LOCATED WITHIN A
 200-FOOT (60 960 MM) WALKING DISTANCE OF THE NEAREST
 WATER'S EDGE OF EACH POOL SERVED BY THE FACILITIES.
 EXCEPTION: WHERE A SWIMMING POOL SERVES ONLY A
 DESIGNATED GROUP OF RESIDENTIAL DWELLING UNITS
 INCLUDING HOTEL ROOMS AND NOT THE GENERAL PUBLIC,
 POOLSIDE SANITARY FACILITIES ARE NOT REQUIRED IF ALL
 LIVING UNITS ARE WITHIN A 200-FOOT (60 960 MM)
 HORIZONTAL RADIUS OF THE NEAREST WATER'S EDGE, ARE NOT
 OVER THREE STORIES IN HEIGHT UNLESS SERVICED BY AN
 ELEVATOR, AND ARE EACH EQUIPPED WITH PRIVATE SANITARY
 FACILITIES.
  
 8) A LIFE SAFTEY PLAN WAS SUBMITTED FOR LEVEL 1 (THE
 GROUND FLOOR). SUBMIT A LIFE SAFETY PLAN FOR THE ROOF
 TOP POOL LEVEL. FBC 107.2.1
  
 9) SHOW COMPLIANCE WITH FBC 454.1.6.2 RINSE SHOWER. A
 MINIMUM OF ONE RINSE SHOWER SHALL BE PROVIDED ON THE
 POOL DECK OF ALL OUTDOOR POOLS WITHIN THE PERIMETER OF
 THE FENCE.
  
 10) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.