2022-06-23 12:13:39 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE SITE SHOWN ON THE COVER SHEET PL0.00 IS NOT THE |
| LOCATION OF THIS PROJECT. THIS PROJECT IS LOCATED AT |
| 4334 N. FLAGLER DRIVE, WEST PALM BEACH, FLORIDA, FBC |
| AMENDMENTS 107.2.1 |
| |
| 2) SUBMIT A COPY OF THE MANUFACTURER'S SPECIFICATIONS |
| AND INSTALLATION INSTRUCTIONS FOR THE ADA POOL LIFT. |
| FBC 107.2.1 |
| |
| 3) POOL IS SHOWN WITH A WATER DEPTH OF LESS THAN 4 |
| FEET. FBC 454.1.2.2.4 POOL DEPTHS. THE MINIMUM WATER |
| DEPTH SHALL BE 3 FEET (914 MM) IN SHALLOW AREAS AND 4 |
| FEET (1219 MM) IN DEEP AREAS. |
| |
| 4) SHOW THAT THERE IS ADEQUATE CLEARANCE AT THE POOL |
| LIFT. FBC 454.1.2.5.6 DISABLED ACCESS. PERMANENT OR |
| PORTABLE STEPS, RAMPS, HANDRAILS, LIFTS OR OTHER |
| DEVICES DESIGNED TO ACCOMMODATE HANDICAPPED INDIVIDUALS |
| IN SWIMMING POOLS MAY BE PROVIDED. LIFTS MOUNTED INTO |
| THE POOL DECK SHALL HAVE A MINIMUM 4-FOOT-WIDE (1219 |
| MM) DECK BEHIND THE LIFT MOUNT. |
| |
| 5) SHOW COMPLIANCE WITH FBC 454.1.3.1.3. POOL WET DECKS |
| SHALL HAVE A MINIMUM UNOBSTRUCTED WIDTH OF 4 FEET (1219 |
| MM) AROUND THE PERIMETER OF THE POOL, POOL CURB, |
| LADDERS, HANDRAILS, DIVING BOARDS, DIVING TOWERS AND |
| SLIDES. |
| |
| 6) SHOW COMPLIANCE WITH FBC 454.1.3.1.5. WALKWAYS SHALL |
| BE PROVIDED BETWEEN THE POOL AND THE SANITARY |
| FACILITIES, AND SHALL BE CONSTRUCTED OF CONCRETE OR |
| OTHER NONABSORBENT MATERIAL HAVING A SMOOTH |
| SLIP-RESISTANT FINISH FOR THE FIRST 15 FEET (4572 MM) |
| OF THE WALKWAY MEASURED FROM THE NEAREST POOL WATER'S |
| EDGE. A HOSE BIBB WITH A VACUUM BREAKER SHALL BE |
| PROVIDED TO ALLOW THE DECK TO BE WASHED DOWN WITH |
| POTABLE WATER. |
| |
| 7) SHOW COMPLIANCE WITH FBC 454.1.6.1 SANITARY |
| FACILITIES. SWIMMING POOLS WITH A BATHING LOAD OF 20 |
| PERSONS OR LESS MAY UTILIZE A UNISEX RESTROOM. POOLS |
| WITH BATHING LOADS OF 40 PERSONS OR LESS MAY UTILIZE |
| TWO UNISEX RESTROOMS OR MEET THE REQUIREMENTS OF TABLE |
| 454.1.6.1. UNISEX RESTROOMS SHALL MEET ALL THE |
| REQUIREMENTS FOR MATERIALS, DRAINAGE AND SIGNAGE AS |
| INDICATED IN SECTIONS 454.1.6.1.1 THROUGH 454.1.6.1.4. |
| EACH SHALL INCLUDE A WATER CLOSET, A DIAPER CHANGE |
| TABLE, A URINAL AND A LAVATORY. POOLS WITH A BATHING |
| LOAD LARGER THAN 40 PERSONS SHALL PROVIDE SEPARATE |
| SANITARY FACILITIES LABELED FOR EACH SEX. THE ENTRY |
| DOORS OF ALL RESTROOMS SHALL BE LOCATED WITHIN A |
| 200-FOOT (60 960 MM) WALKING DISTANCE OF THE NEAREST |
| WATER'S EDGE OF EACH POOL SERVED BY THE FACILITIES. |
| EXCEPTION: WHERE A SWIMMING POOL SERVES ONLY A |
| DESIGNATED GROUP OF RESIDENTIAL DWELLING UNITS |
| INCLUDING HOTEL ROOMS AND NOT THE GENERAL PUBLIC, |
| POOLSIDE SANITARY FACILITIES ARE NOT REQUIRED IF ALL |
| LIVING UNITS ARE WITHIN A 200-FOOT (60 960 MM) |
| HORIZONTAL RADIUS OF THE NEAREST WATER'S EDGE, ARE NOT |
| OVER THREE STORIES IN HEIGHT UNLESS SERVICED BY AN |
| ELEVATOR, AND ARE EACH EQUIPPED WITH PRIVATE SANITARY |
| FACILITIES. |
| |
| 8) A LIFE SAFTEY PLAN WAS SUBMITTED FOR LEVEL 1 (THE |
| GROUND FLOOR). SUBMIT A LIFE SAFETY PLAN FOR THE ROOF |
| TOP POOL LEVEL. FBC 107.2.1 |
| |
| 9) SHOW COMPLIANCE WITH FBC 454.1.6.2 RINSE SHOWER. A |
| MINIMUM OF ONE RINSE SHOWER SHALL BE PROVIDED ON THE |
| POOL DECK OF ALL OUTDOOR POOLS WITHIN THE PERIMETER OF |
| THE FENCE. |
| |
| 10) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |