2022-07-05 06:34:28 | 2ND PLUMBING REVIEW |
| |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. SHEET A-5 - BATHROOM NEAR CLUB ROOM - 2020 FRC |
| P3108.1 - THE BAR SINK IN THE CLUB ROOM SHALL DISCHARGE |
| DOWNSTREAM OF THE WET VENT SYSTEM. ONLY BATHROOM GROUP |
| FIXTURES ARE ALLOWED TO DISCHARGE WITHIN THE WET VENT. |
| ALL OTHER FIXTURES MUST DISCHARGE DOWNSTREAM OF THE WET |
| VENT SYSTEM. PLEASE RECONFIGURE AND RESUBMIT. |
| CORRECTIONS DO NOT COMPLY. THE BAR SINK MUST DISCHARGE |
| DOWNSTREAM OF THE SHOWER IN ORDER TO "WET VENT" THE |
| SHOWER AND/OR WATER CLOSET. |
| |
| |
| 2. DONE |
| |
| 3. DONE |
| |
| 4. SHEET A-5 - POWDER BATH - 2020 FRC P3108.1 - THE |
| LAUNDRY TUB AND THE AUTOMATIC CLOTHES WASHER ARE |
| DISHCHARGING INTO THE WET VENT FOR THE POWDER BATH. |
| ONLY BATHROOM GROUP FIXTURES ARE ALLOWED TO DISCHARGE |
| WITHIN THE WET VENT. ALL OTHER FIXTURES MUST DISCHARGE |
| DOWNSTREAM OF THE WET VENT SYSTEM. PLEASE RECONFIGURE |
| AND RESUBMIT. |
| CORRECTIONS DO NOT COMPLY. - WATER CLOSET IS STILL |
| BEING VENTED BY LAUNDRY TUB, WASHER AND BAR SINK. ONLY |
| BATHROOM GROUP FIXTURES CAN BE INCLUDED IN THE WET VENT |
| FOR OTHER BATHROOM GROUP FIXTURES. ALSO, LOOP VENT IS |
| MIS-LABELED. THIS IS NOT A LOOP VENT, BUT RATHER A |
| BRANCH VENT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |