Plan Review Notes
Plan Review Notes For Permit 22040494
Permit Number 22040494
Review Stop P
Sequence Number 2
Notes
Date Text
2022-07-05 06:34:282ND PLUMBING REVIEW
  
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. SHEET A-5 - BATHROOM NEAR CLUB ROOM - 2020 FRC
 P3108.1 - THE BAR SINK IN THE CLUB ROOM SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT SYSTEM. ONLY BATHROOM GROUP
 FIXTURES ARE ALLOWED TO DISCHARGE WITHIN THE WET VENT.
 ALL OTHER FIXTURES MUST DISCHARGE DOWNSTREAM OF THE WET
 VENT SYSTEM. PLEASE RECONFIGURE AND RESUBMIT.
 CORRECTIONS DO NOT COMPLY. THE BAR SINK MUST DISCHARGE
 DOWNSTREAM OF THE SHOWER IN ORDER TO "WET VENT" THE
 SHOWER AND/OR WATER CLOSET.
  
  
 2. DONE
  
 3. DONE
  
 4. SHEET A-5 - POWDER BATH - 2020 FRC P3108.1 - THE
 LAUNDRY TUB AND THE AUTOMATIC CLOTHES WASHER ARE
 DISHCHARGING INTO THE WET VENT FOR THE POWDER BATH.
 ONLY BATHROOM GROUP FIXTURES ARE ALLOWED TO DISCHARGE
 WITHIN THE WET VENT. ALL OTHER FIXTURES MUST DISCHARGE
 DOWNSTREAM OF THE WET VENT SYSTEM. PLEASE RECONFIGURE
 AND RESUBMIT.
 CORRECTIONS DO NOT COMPLY. - WATER CLOSET IS STILL
 BEING VENTED BY LAUNDRY TUB, WASHER AND BAR SINK. ONLY
 BATHROOM GROUP FIXTURES CAN BE INCLUDED IN THE WET VENT
 FOR OTHER BATHROOM GROUP FIXTURES. ALSO, LOOP VENT IS
 MIS-LABELED. THIS IS NOT A LOOP VENT, BUT RATHER A
 BRANCH VENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  