Plan Review Notes For Permit 22040404 |
Permit Number |
22040404 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-06-09 10:22:36 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1/0 CONDUCTORS FOR SERVICE DOES NOT APPEAR TO BE LARGE | | ENOUGH. LOAD CALCULATION SUBMITTED IS NOT DONE IN | | ACCORADANCE WITH ARTICLE 220 OF THE NEC. | | | | | | PLEASE SUBMIT A LOAD CALCULATION THAT IS DONE PER | | ARTICLE 220. |
|