Plan Review Notes For Permit 22040404
Permit Number 22040404
Review Stop M
Sequence Number 1
Notes
Date Text
2022-04-19 13:40:26PLAN DENIED
 1) REFER TO SECTION 107 FBC 2020 PROVIDE EQUIPMENT
 SCHEDULE ON PLAN.
 2) REFER TO SECTION R403.6 MECHANICAL VENTILATION
 MANDATORY.
 2020 FBC ENERGY. AUTOMATIC DAMPER REQUIRED FOR FRESH
 AIR
 3) REFER TO SECTION M1602 #4 RETURN AIR SHALL NOT BE
 TAKEN FROM
 BATHROOM. 2020 RESIDENTIAL CODE
 4) REFER TO COMMENT #2 FOR FRESH AIR IN ACCESSORY
 STRUCTURE.