Plan Review Notes For Permit 22040404 |
Permit Number |
22040404 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-03 08:35:51 | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) WHAT SIZE MAIN IS ON FEEDER TO PANEL "A" ? 215.5 | | | | 2) GROUNDING ELECTRODE SYSTEM REQUIRED AT ACCESSORY | | STRUCTURE 250.32(A) | | | | 3) CARBON MONOXIDE DETECTOR REQUIRED FBC R315 |
|