 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) WHAT SIZE MAIN IS ON FEEDER TO PANEL "A" ? 215.5
  
 2) GROUNDING ELECTRODE SYSTEM REQUIRED AT ACCESSORY
 STRUCTURE 250.32(A)
  
 3) CARBON MONOXIDE DETECTOR REQUIRED FBC R315