2022-04-28 15:24:281ST PLUMBING REVIEW
  
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. MASTER BATHROOM - 2020 FRC P3108.1 - THE MASTER
 BATHROOM VENTING IS NOT TO CODE. THE SHOWER AND WATER
 CLOSET ARE ON THE HIGH SIDE OF A VENTED BRANCH
 CONNECTION AND ONLY ONE TRAP IS ALLOWED UPSTREAM OF THE
 VENTED FIXTURE. ALSO, THE VENT FOR THE TUB IS A DRY
 VENT AND IS NOT ALLOWED TO BE. DRY VENTS MUST BE
 VERTICAL UNTIL THEY ARE AT LEAST 6" ABOVE THE
 FIXTURE(S) SERVED (P3104.4).
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  