2022-06-25 08:16:231ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. MASTER BATH - 2020 FPC P3108.2.1 - THE SHOWER AND
 WATER CLOSET ARE NOT VENTED CORRECTLY. THERE ARE TWO
 TRAPS ON THE UPSTREAM SIDE OF THE VENTED FIXTURE'S
 CONNECTION TO THE WET VENT. ONLY ONE IS ALLOWED
 UPSTREAM. PLEASE RECONFIGURE.
  
 2. 2017 WPB AMENDS 107.2.1 - YOU ARE DETAILING A GAS
 WATER HEATER ON PAGE P-1, BUT ON THE ELECTRICAL PAGE
 SHOWING A 240 OUTLET AT THAT LOCATION AND ARE NOT
 SHOWING ANY GAS IN THE PLANS. PLEASE CORRECT THE DETAIL
 IF AN ELECTRIC WATER HEATER IS PLANNED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  