Plan Review Notes
Plan Review Notes For Permit 22040320
Permit Number 22040320
Review Stop M
Sequence Number 2
Notes
Date Text
2022-05-05 06:00:11THE MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THE
 SAME ADDRESS WAS SUBMITTED. EACH HAS A DIFFERENT
 MINIMUM SIZE MECHANICAL SYSTEM STATED. THERE WAS NO
 ENERGY CALCULATIONS SUBMITTED AND THE SKETCH PROVIDED
 IN THE MECHANICAL EQUIPMENT SIZING CALCULATIONS DOES
 NOT SHOW THE MECHANICAL SYSTEM LOCATIONS OR ANY DUCT
 SIZES. THIS SKETCH WILL NOT BE CONSIDERED A MECHANICAL
 DRAWING OF THE INSTALLATION.
 PLEASE ADDRESS THE COMMENTS BELOW FROM THE 1ST CYCLE
 PLAN REVIEW FOR THIS PROJECT.
  
 1ST REVIEW FMC
 PERMIT: 22040320
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPLICATION STATES THE SCOPE OF THIS PROJECT AS,
 A/C CHANGE OUT AND DUCT WORK. WE HAVE NO RECORD THAT A
 MECHANICAL SYSTEM IS INSTALLED AT THIS ADDRESS. PLEASE
 PROVIDE ENERGY CALCULATIONS, MECHANICAL EQUIPMENT
 SIZING CALCULATIONS AND A MECHANICAL DRAWING SHOWING
 THE COMPLETE NEW SYSTEM INSTALLATION. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  