2022-07-27 10:55:214TH PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. NOT ADDRESSED. LAUNDRY MUST DISCHARGE DOWNSTREAM OF
 THE BATHROOM GROUP FIXTURES. (LOWER THAN THE WATER
 CLOSETS ON THE STACK) 2020 FPC 912.1.1 - ONLY THE
 BATHROOM GROUP FIXTURES CAN CONNECT INSIDE THIS WET
 VENT AREA, THE NEW WASHING MACHINE MUST BE DOWNSTREAM
 (LOWER) THAN THE LAST BATHROOM GROUP FIXTURE WHEN
 CONNECTING TO THE STACK.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  