2022-07-20 14:01:231ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 912.1.1 - IN VERTICAL WET VENTS, WATER
 CLOSETS SHALL CONNECT AT THE SAME LEVEL AS OTHER WATER
 CLOSETS AND "ALL OTHER FIXTURE DRAINS SHALL CONNECT
 ABOVE OR AT THE SAME LEVEL AS THE WATER CLOSET. THE TUB
 AND NEW SHOWER CANNOT CONNECT BELOW THE WATER CLOSET.
  
 2. 2020 FPC 912.1.1 - ONLY THE BATHROOM GROUP FIXTURES
 CAN CONNECT INSIDE THIS WET VENT AREA, THE NEW WASHING
 MACHINE MUST BE DOWNSTREAM (LOWER) THAN THE LAST
 BATHROOM GROUP FIXTURE WHEN CONNECTING TO THE STACK.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  