Plan Review Notes For Permit 22040264
Permit Number 22040264
Review Stop B
Sequence Number 3
Notes
Date Text
2022-06-03 13:16:45JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5;
 EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (170). ZONE 3 IS MARKED ?N/A? WHICH
 INDICATES SYSTEM CANNOT BE USED WITHIN THE PRESSURE
 ZONE. THE CORRECT EXPOSURE FOR THE LISTED ADDRESS IS
 EXPOSURE C. PLEASE SELECT THE CORRECT OPTIONS.
 2. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 NO.20-1214.01 TILE BOND IS NOT AN APPROVED TILE
 ADHESIVE AS PER THE MIAMI-DADE NOA NO. 18-0119.03
 VERREA BARREL TILE GRADE 1. PROVIDE A COMPLETE SET OF
 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR AN
 APPROVED ROOFING TILE ADHESIVE TO BE USED. (POLYSET
 AH-160)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  
  