2022-06-03 13:16:45 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5; |
| EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); |
| ULTIMATE WIND SPEED (170). ZONE 3 IS MARKED ?N/A? WHICH |
| INDICATES SYSTEM CANNOT BE USED WITHIN THE PRESSURE |
| ZONE. THE CORRECT EXPOSURE FOR THE LISTED ADDRESS IS |
| EXPOSURE C. PLEASE SELECT THE CORRECT OPTIONS. |
| 2. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA |
| NO.20-1214.01 TILE BOND IS NOT AN APPROVED TILE |
| ADHESIVE AS PER THE MIAMI-DADE NOA NO. 18-0119.03 |
| VERREA BARREL TILE GRADE 1. PROVIDE A COMPLETE SET OF |
| 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR AN |
| APPROVED ROOFING TILE ADHESIVE TO BE USED. (POLYSET |
| AH-160) |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |
| |