Plan Review Notes
Plan Review Notes For Permit 22040230
Permit Number 22040230
Review Stop P
Sequence Number 1
Notes
Date Text
2022-04-28 15:05:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22040230 3099 GIN BERRY WAY POOL
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. RE: HYDRAULIC (TDH) CALCULATIONS; PER WPB FBC 107.2.
 1, FBC RES R4501.7.3 AND APSP-7-2013, SHALL INCLUDE THE
 HEAD LOSS FOR THE POOL HEATER, FILTER AND ALL OTHER
 INLINE APPURTENANCES AS WELL AS THE VALVES AND
 FITTINGS. ADDITIONALLY, ALL EQUIPMENT SUBMITTALS SHALL
 BE CLEAR, EASILY READ AND SHALL INCLUDE ALL PERTINENT
 TECHNICAL INFORMATION INCLUDING BUT NOT LIMITED TO
 HYDRAULIC FLOW AND HEAD LOSS. PUMP IS NOT INCLUDED IN
 CALCULATIONS.
 FURNISHED HYDRAULIC CALCULATIONS DO NOT INCLUDE ANY
 FITTINGS. PER WPB FBC 107.2.1, PROVIDE COMPLETE
 CALCULATIONS. SUBMIT COPY OF CALCULATIONS ON RECOGNIZED
 FORM SUCH AS APSP/ANSI-7 TO SUPPLEMENT PLAN SHEET 4 OF
 5 TDH CALCULATIONS WORKSHEET.
  
  
 2. PROVIDED EQUIPMENT SPECIFICATIONS ARE LESS THAN
 CLEAR AND DO NOT PROVIDE PERTINENT INFORMATION. PER WPB
 FBC 107.2.1, PROVIDE MANUFACTURER'S SPECIFICATION AND
 INSTALLATION MANUAL FOR ALL IN-LINE POOL EQUIPMENT IN
 THE PIPING SYSTEM. INLINE EQUIPMENT SPECS IN THE PIPING
 SYSTEM (IE. FILTER, HEATER, ETC. NEED TO PROVIDE HEAD
 LOSS TO SHOW WHERE ENGINEER GOT CALCS FOR TDH). ALL
 EQUIPMENT SUBMITTALS SHALL BE CLEAR, EASILY READ AND
 SHALL INCLUDE ALL PERTINENT TECHNICAL INFORMATION
 INCLUDING BUT NOT LIMITED TO SPECIFIC MODEL NUMBER,
 HYDRAULIC FLOW AND HEAD LOSS
  
  
 3. PROVIDE SPECS FOR SKIMMERS. THEY NEED TO BE DESIGNED
 TO PREVENT ENTRAPMENT. SEE FBC RES R4501.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH REQUIREMENTS OF ANSI/APSP/ICC 7.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
  