2022-05-13 09:22:33 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22040221 |
| 9/28/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) FAIR HOUSING ACT COMPLIANCE: THE CONDOMINIUMS AT |
| 1801 N FLAGLER WERE DESIGNED AND CONSTRUCTED IN |
| COMPLIANCE THE FAIR HOUSING ACT DESIGN MANUAL, |
| THEREFORE THE PROPOSED ALTERATION TO BATHROOMS IN UNIT |
| 533 SHALL ALSO BE IN COMPLIANCE. PLEASE PROVIDE CODE |
| DATA INFORMATION ON THAT INCLUDES COMPLIANCE WITH THE |
| FAIR HOUSING ACT DESIGN MANUAL AND THE CURRENT FLORIDA |
| BUILDING CODES- 2020 7TH EDITION. THE FAIR HOUSING |
| ACCESSIBILITY GUIDELINES ARE INCLUDED IN THE FLORIDA |
| ACCESSIBILITY CODE- 2020 7TH EDITION AND THE FAIR |
| HOUSING DESIGN ACT MANUAL. |
| |
| 2) MASTER AND HALL BATHS: PLEASE REFER TO PAGES 7.56- |
| 7.59 OF THE FHDA MANUAL AND INDICATE ON THE PLANS THE |
| REQUIRED 30X48-INCH CLEAR FLOOR SPACES POSITONED FOR |
| PARALLEL APPROACHES TO THE SHOWERS. PLEASE NOTE THAT NO |
| FIXTURES ARE ALLOWED TO OVERLAP THE CLEAR FLOOR SPACES |
| REQUIRED FOR THE SHOWERS. THE BATHROOM LAYOUTS MAY BE |
| NON-COMPLIANT BECAUSE THERE ARE TOILETS ADJACENT TO THE |
| SHOWERS. |
| |
| 3) MASTER AND HALL BATHS: REFER TO PAGES 6.12- 6.13 OF |
| THE FHDA MANUAL AND PROVIDE AN ELEVATION DETAIL SHOWING |
| THE SHOWER CONTROLS LOCATION, AND THE GRAB BAR AND SEAT |
| REINFORCEMENT DETAILS. SHOW THE LENGTHS, WIDTHS AND |
| HEIGHTS AND THE TYPE OF REINFORCEMENT MATERIAL TO BE |
| USED. SEE SECTION 603.1 FOR ALLOWABLE MATERIALS IN |
| NON-COMBUSTIBLE BUILDINGS. |
| |
| PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| COPY OF THE FAIR HOUSING AFFIDAVIT. |
| |
| 4) RELOCATING THE SHOWER DRAIN OUTLETS MAY REQUIRE THE |
| FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING |
| STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A |
| NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET- |
| SECTION 107.2.1 WPB. |
| |
| 5) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| FBC P AND SECTION 714.4.1.2 FBC B. |
| |
| 6) THE SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHOW BE |
| ON THE DRAWINGS- SEC.107.2.1 WPB, AND FL. STATUTES |
| 471.003(2)(H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |