Plan Review Notes
Plan Review Notes For Permit 22031582
Permit Number 22031582
Review Stop M
Sequence Number 2
Notes
Date Text
2022-05-17 10:09:352ND REVIEW FMC
 PERMIT: 22031582
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS ARE FOR A NEW FINISHED
 BUILDING- WAREHOUSE. THE ENERGY CALCULATIONS DO NOT
 SHOW ANY INSULATION VALUES FOR THIS BUILDING I.E.
 WALLS, FLOORS, ROOF, DOORS. THIS MUST BE INCLUDED IF
 THIS BUILDING IS TO BE CONDITIONED. FEC C402
  
 2) THE PLAN SUBMITTED BY JOHN C. CASSIDY AND THE PLAN
 SUBMITTED BY ENERGY HOUSE TECHNOLOGY DO NOT MATCH. THE
 ENERGY HOUSE PLAN SHOWS SUPPLY GRILLES IN THE ROOMS IN
 FRONT OF THE WAREHOUSE AREAS. IT SHOWS BATHROOMS WITH
 NO EXHAUST VENTILATION. THE PLAN SUBMITTED BY JOHN C.
 CASSIDY DOES NOT SHOW ANYTHING IN THESE AREAS. THIS IS
 A NEW BUILDING, PROVIDE A COMPLETE DESIGN FOR THIS
 BUILDING INCLUDING THE OUTDOOR AIR CALCULATIONS AS
 DETERMINED BY FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 3) REVISE THE PLAN TO SHOW THE CONDENSING UNITS TIE
 DOWN METHOD AND SHOW HOW THE CONDENSING UNITS WILL BE
 PROTECTED FROM DAMAGE. FMC 303.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  