2022-05-17 10:09:35 | 2ND REVIEW FMC |
| PERMIT: 22031582 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE ENERGY CALCULATIONS ARE FOR A NEW FINISHED |
| BUILDING- WAREHOUSE. THE ENERGY CALCULATIONS DO NOT |
| SHOW ANY INSULATION VALUES FOR THIS BUILDING I.E. |
| WALLS, FLOORS, ROOF, DOORS. THIS MUST BE INCLUDED IF |
| THIS BUILDING IS TO BE CONDITIONED. FEC C402 |
| |
| 2) THE PLAN SUBMITTED BY JOHN C. CASSIDY AND THE PLAN |
| SUBMITTED BY ENERGY HOUSE TECHNOLOGY DO NOT MATCH. THE |
| ENERGY HOUSE PLAN SHOWS SUPPLY GRILLES IN THE ROOMS IN |
| FRONT OF THE WAREHOUSE AREAS. IT SHOWS BATHROOMS WITH |
| NO EXHAUST VENTILATION. THE PLAN SUBMITTED BY JOHN C. |
| CASSIDY DOES NOT SHOW ANYTHING IN THESE AREAS. THIS IS |
| A NEW BUILDING, PROVIDE A COMPLETE DESIGN FOR THIS |
| BUILDING INCLUDING THE OUTDOOR AIR CALCULATIONS AS |
| DETERMINED BY FMC 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 3) REVISE THE PLAN TO SHOW THE CONDENSING UNITS TIE |
| DOWN METHOD AND SHOW HOW THE CONDENSING UNITS WILL BE |
| PROTECTED FROM DAMAGE. FMC 303.4 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |