Plan Review Notes For Permit 22031517 |
Permit Number |
22031517 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-16 09:27:18 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 107, A SURVEY SHOWING ELEVATIONS IS REQUIRED. | | | | 2. FBC 107, PROVIDE A DRAINAGE PLAN. THE SITE WALL | | APPEARS TO BE FOR THE PURPOSE OF RETAINING SOIL, BUT | | THAT CANNOT BE EVALUATED WITHOUT A COMPLETE DRAINAGE | | PLAN. ALTERNATIVELY, THE PLAN CAN BE MODIFIED TO NOTE | | THAT ALL FILL WILL BE INCLUDED IN THE SFD PERMIT, THIS | | PERMIT WILL BE ISSUED AT APPLICANT'S RISK. | | | | 3. FBC 107, REVISE PLAN TO CLARIFY HOW THE BLOCK WILL | | KEEP WATER FROM SEEPING THROUGH ONTO THE ADJACENT | | PROPERTY. STUCCO IS SHOWN ON ONE SIDE ONLY. NO PAINT OR | | WATERPROOFING IS SHOWN ON EITHER SIDE OF THE WALL. | | | | 4. FBC 107 STAIRS, SLAB ARE SHOWN. REMOVE OR CROSS OFF | | OF THE PLAN AS THIS IS NOT WITHIN THE SCOPE OF THIS | | PERMIT. | | | | 5. REVISE PLAN TO STATE WIND DESIGN CRITERIA AND FLOOD | | DESIGN CRITERIA, FBC R 301, R 322. |
|