2022-04-27 06:02:511ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. MASTER BATH - 2020 FRC P3108.1 - THE CLOTHES WASHER
 CANNOT VENT THE WATER CLOSET OR THE SHOWER. ONLY
 BATHROOM GROUP FIXTURES CAN BE USED AS WET VENTS. ALL
 FIXTURES THAT ARE NOT INCLUDED IN THE BATHROOM GROUP
 SHALL DISCHARGE DOWNSTREAM OF THE WET VENT SYSTEM.
  
 2. HALF BATH - 2020 FRC P3108.1 - THE WATER CLOSET'S
 FIXTURE DRAIN CANNOT BE TIED INTO THE EXISTING
 HORIZONTAL WITHOUT A VENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  