Plan Review Notes
Plan Review Notes For Permit 22031470
Permit Number 22031470
Review Stop E
Sequence Number 1
Notes
Date Text
2022-05-09 13:39:12ELECTRIC REVIEW FAILED
 1) DIAGRAM INCORRECTLY DETAILS 1/0 SERVICE CONDUCTORS
 FROM METER TO DISCONNECT TO PANEL A . PLEASE CORRECT TO
 CORRECT SIZED 2/0 CU CONDUCTORS AS PER NEC NEC 310.15
 (B)(7)(2)
 2) RISER DIAGRAM DOES NOT DETAIL OVERCURRENT PROTECTION
 FEEDING PANEL B. PLEASE DETAIL OVERCURRENT PROTECTION
 TO CORRECTLY PROTECT 1/0 FEEDER CONDUCTORS FROM PANEL A
 TO PANEL B. NEC 240.4
 3) IT APPEARS PANEL A IS LOCATED IN A CLOSET. PLEASE
 DETAIL HOW THIS IS CODE COMPLIANT WITH NEC 240.24 (D)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  