Plan Review Notes
Plan Review Notes For Permit 22031379
Permit Number 22031379
Review Stop E
Sequence Number 1
Notes
Date Text
2022-04-19 09:51:48ELECTRIC REVIEW FAILED
 1) PLEASE CORRECT PLAN DESCRIPTION FOR SHEET E3.1 TO
 DELETE PANEL SCHEDULES, AND, CORRECT PLAN DESCRIPTION
 FOR SHEET E4.1 TO STATE PANEL SCHEDULES. FBC 107.2
 2) PLEASE INCLUDE A NOTE STATING POOLS,GENERATORS AND
 LOW VOLTAGE WIRING REQUIRE A SEPERATE PERMIT
 3) PLEASE DETAIL ON DRAWINGS INDICATING WHAT THE GREYED
 OUT AREAS ON ELECTRICAL FLOOR PLANS DESCRIBES . FBS
 107.2
 4) PLEASE HAVE THE ENGINEER/ ARCHITECT OF RECORD SIGN
 AND SEAL ALL DRAWINGS AS REQUIRED.FS471/FS481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  