Plan Review Notes
Plan Review Notes For Permit 22031179
Permit Number 22031179
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-24 16:39:45NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SURVEY.
  
 2) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOFING SYSTEM.
  
 3) ADDRESS ON THE DRAWINGS NEEDS TO MATCH THE ADDRESS
 ON THE BUILDING PERMIT APPLICATION.
  
 4) DRAWING SP-1 SHOWS THE CODE VERSION USED FOR DESIGN
 AS 2017 FBC - SHOULD BE 2020 FBC
  
 5) SITE PLAN SHOWS BUILDING SETBACK AT 3' 2" - THE
 BUILDING OVERHANG (PROJECTION) ON THAT SIDE WILL NEED
 TO BE A MINIMUM OF 2' FROM THE PROPERTY LINE AND BE
 FIRE RATED PER FBC TABLE R302.1
 WITH A 1' 4" OVERHANG YOU ARE 1' 10" FROM THE PROPERTY
 LINE - MUST BE AT LEAST 2' FROM THE PROPERTY LINE.
  
  