Notes
Date Text
2022-04-22 13:47:19FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FOR A FEEDER RATED 100 THROUGH 400 AMPERES, THE FEEDER
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING
 THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING
 UNIT
 IN A TWO-FAMILY OR MULTIFAMILY DWELLING, SHALL BE
 PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT
 OF THE FEEDER
 RATING.