Plan Review Notes For Permit 22031010 |
Permit Number |
22031010 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-24 09:17:56 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | DEMO PERMIT PER FLORIDA BUILDING | | CODE, BUILDING 3303: | | | | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) | | RELEASE OF SERVICE CONFIRMATION. | | | | 3. WATERDOWN METHOD DURING DEMO: | | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED | | INFPRMATION OF THE WATER TRUCK SUCH AS: THE | | GALLON CAPACITY OF THE WATER TANK AND A LETTER | | INCLUDING A STATEMENT THAT THE WATER | | USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY | | AND WILL BE ON-SITE AT ALL TIMES | | DURING DEMOLITION. | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | THEN A PARTIAL RELEASE WILL BE NOTED | | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS | | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE | | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY | | THE CITY?S UTILITIES DEPT, 561-822-2244. FAX THE | | COMPLETED "DEMOLITION APPLICATION" FORM TO | | 561-822-2183. | | | | |
|