2022-03-21 11:37:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE ARE INDICATIONS OF HALLWAY CEILING REPAIR. |
| |
| FORE THE OFFICIAL RECORD, IS IT A REPAIR OR A DEMO AND |
| REPLACEMENT? |
| |
| PLEASE PROVIDE SECIFIC DETAILS. |
| |
| |
| 2) THERE ARE INDICATIONS OF A REPAIR OF A CEILING IN A |
| HALLWAY. |
| |
| THERE IS NO LISTED/SPECIFICATION CALLOUT OF THE |
| REQUIRED FIRE RATING OF THIS HALLWAY THAT THE REPAIR IS |
| REQUIRED TO MEET. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ORIGINAL |
| FIRE RATING OF THIS HALLWAY AND LISTED REPAIR THAT THE |
| REPAIR IS REQUIRED TO MEET. |
| |
| |
| 3) THE CEILING WORK MAY INVOLVE THE FIRE SPRINKLER |
| HEADS IN SOME WAY. |
| |
| ANY WORK ON THE FIRE SPRINKLER HEADS/SYTEM EQUIPMENT, |
| INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMIT & |
| SHOP DRAWINGS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| |
| |
| |
| 4) THE CEILING WORK MAY INVOLVE THE FIRE ALARM |
| EQUIPMENT IN SOME WAY. |
| |
| ANY WORK ON THE FIRE ALARM EQUIPMENT, INCLUDING DEMO, |
| SHALL BE DONE UNDER SEPARATE PERMIT & SHOP DRAWINGS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| |
| |
| |
| 5) THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE |
| MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| |
| |
| |
| 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |