Plan Review Notes
Plan Review Notes For Permit 22030889
Permit Number 22030889
Review Stop E
Sequence Number 1
Notes
Date Text
2022-04-11 11:09:58ELECTRIC REVIEW FAILED
 1)RISER DIAGRAM APPEARS TO BE INCORRECT FOR A 400-AMP
 SERVICE. PLEASE CORRECT AS APPLICABLE. NEC 215.5
 2) PLEASE PROVIDE ELECTRICAL LOAD CALCULATIONS. NEC
 215.5
 3) IT APPEARS EQUIPMENT INFORMATION IS MISSING AND NOT
 LOCATED, EXAMPLES, METER, PANEL, REFRIGERATOR, AIR
 CONDITIONING, ETC. PLEASE CORRECT AS APPLICABLE. FBC
 107.2
 4)KITCHEN ISLAND APPEARS TO BE MISSING REQUIRED
 RECEPTACLES. PLEASE CORRECT AS PER NEC 210.52
 PLEASE INCLUDE A NOTE ON PLAN THAT POOL, LOW VOLTAGE,
 SITE LIGHTING AND GENERATORS REQUIRE A SEPARATE PERMIT
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  