Plan Review Notes For Permit 22030866 |
Permit Number |
22030866 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-18 08:50:16 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | | | 1. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR | | THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL | | HEIGHT(S). | | 2. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT | | COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL | | AND CHAPTER 11 OF THE 2020 FBC-PLUMBING | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | |
|